[8-10 Troubleshooting Inverter Problems ]
46
-
chapter 8
BS_08_E
8 Troub
le
sho
oting Bas
ed on Ob
ser
ved
Sy
mp
toms
8-10-6
Checking the Converter for Damage during Compressor Operation
8-10-7
Checking the Fan Motor for Ground Fault and Coil Resistance Problems
8-10-8
Checking the Fan Board Error Detection Circuit at No Load
Items to be checked
Phenomena
Remedy
(1)
Operate the outdoor unit.
1)
BUS voltage does not boost (does
not change) BUS voltage does not
boost to approximately between
650 and 750 VDC, or the following
errors are detected.
Error code : 4220
Detail code : 123
Replace the inverter board.
(2)
Check the BUS voltage after the
converter circuit went into oper-
ation and the BUS voltage has
boost.
*The voltage generally boost at
or above 80 rps, depending on
the power source voltage.
2)
An overcurrent error occurs after
converter circuit goes into opera-
tion.
Error code : 4250
Detail code : 121,122
a.If the problem persists after startup, re-
place the inverter board.
b.If the problem persists after replacing
the inverter board, replace the DCL.
3)
An overvoltage error occurs after
converter circuit goes into opera-
tion.
Error code : 4220
Detail code : 109,110,112
a.If the problem persists after startup, re-
place the inverter board.
b.If the problem persists after replacing
the inverter board, replace the DCL.
4)
No problems were found with items
1) through 3).
Normal
Items to be checked
Phenomena
Remedy
Remove fan motor winding. Check
insulation resistance and coil resis-
tance.
1)
Fan motor insulation failure.
If < 1 M
Ω
, Defect.
Change fan motor.
2)
Fan motor wire failure.
Target coil resistance: Approx. 10
Ω
.
(Changes with temperature)
Change fan motor.
Items to be checked
Phenomena
Remedy
(1)
Stop the unit.
Turn off the breaker.
*Be sure to turn off the power.
1)
An error other than current sensor er-
ror (5305, 5306: Detail code 135) is
detected during operation.
Replace the fan board.
(2)
Disconnect the output wiring
to the fan motor.
Disconnect connector
RYFAN1. (On a model with
two fan motors, RYFAN1 cor-
responds to the right fan and
RYFAN2 corresponds to the
left fan (when seen from the
front).)
2)
Current sensor fault
Error code: 5305, 5306
Detail code: 135
Normal
*When done checking, reconnect all
connectors as they were. Unless
they are properly reconnected, cur-
rent sensor fault will not be resolved.
(3)
Turn on the breaker.
(4)
Operate the unit.
0000004986.BOOK 46 ページ 2019年5月9日 木曜日 午後6時22分
Содержание City Multi CMH-WM250V-A
Страница 1: ......
Страница 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Страница 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Страница 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Страница 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Страница 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Страница 147: ... 5 3 Hydro Unit Control 28 chapter 5 BS_05_E 5 Control 0000004980 BOOK 28 ページ 2019年5月9日 木曜日 午後6時18分 ...
Страница 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Страница 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Страница 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Страница 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Страница 436: ......