[4-2 Outdoor Unit Circuit Board Components ]
BS_04_E
chapter 4 -
11
4 Ele
c
tr
ic
al
Comp
onen
ts
a
nd Wiring Diagra
ms
(3) PUHY-(E)M500YNW-A1
1) When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.
Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that
the voltage across pins 1 and 5 of connector RYPN has dropped to 20 VDC or less. It takes about 10 minutes to discharge
electricity after the power supply is turned off.
2) A Faston terminal on the inrush current resistor has a locking function. Make sure the cable heads are securely locked in
place. Press the tab on the terminals to remove them.
3) Control box houses high temperature parts. Be well careful even after turning off the power source.
4)
Perform the service after disconnecting the relay connector (RYFAN1, RYFAN2). Before plugging in or unplugging
connectors, check that the outdoor unit fan is not rotating and that the voltage across pins 1 and 5 of connector
RYPN is 20 VDC or less. The capacitor may collect a charge and cause an electric shock when the outdoor unit fan
rotates in windy conditions.
Refer to the wiring nameplate for details.
5) After servicing, reconnect the relay connector (RYFAN1, RYFAN2) of the fan as it was.
6) When the power is turned on, the compressor is energized even while it is not operating. Before turning on the power, discon-
nect all power supply wires from the compressor terminal block, and measure the insulation resistance of the compressor.
Check the compressor for a ground fault. If the insulation resistance is 1.0 M
Ω
or above, connect all power supply wires to the
compressor and turn on the power to the outdoor unit. The liquid refrigerant in the compressor will evaporate by energizing
the compressor.
C100-C109
Smoothing capacitor
SC-W
Inverter output (W)
SC-V
Inverter output (V)
SC-U
Inverter output (U)
SC-B
Bus voltage output (P)
SC-L3
Input (L3)
SC-L2
Input (L2)
SC-L1
Input (L1)
IGBT (rear)
CT-3
Current sensor
(Direct bus current)
SC-L
Bus voltage output (P)
CNCTIB
DC current sensor input
(CT-3)
CNCTIA
DC current sensor output
(CT-3)
CNRY
12 VDC
GND
(Power-supply
board)
CN2
Serial communication signal
Signal input
GND (MAIN circuit board)
Signal output
GND (MAIN circuit board)
CN19V
18 VDC
GND
CNTH
DCL temperature
thermistor input
CNCT2
Connects to ACCT
with lead wire
CN-P, CN-N
Connects to
connector RYPN
R127
Overcurrent
detection
resistor
LED1
Lit: Inverter operation
Blinking: Inverter error
LED4
Lit: Microcomputer is energized.
Unlit: Microcomputer is not energized.
LED102
Lit: Relay drive power
is supplied.
Unlit: Relay drive power
is not supplied.
F1
250 VAC fuse
3.15 A
0000004976.BOOK 11 ページ 2019年5月8日 水曜日 午後2時57分
Содержание City Multi CMH-WM250V-A
Страница 1: ......
Страница 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Страница 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Страница 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Страница 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Страница 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Страница 147: ... 5 3 Hydro Unit Control 28 chapter 5 BS_05_E 5 Control 0000004980 BOOK 28 ページ 2019年5月9日 木曜日 午後6時18分 ...
Страница 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Страница 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Страница 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Страница 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Страница 436: ......