[7-8 Error Code Definitions and Solutions: Codes [6000 - 6999] ]
BS_07_E
chapter 7 -
79
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-8-21
Error Code [6840]
1. Error code definition
Indoor-outdoor communication: Reception error
2. Error definition and error detection method
Abnormal if indoor controller board could not receive any signal normally for 6 minutes after turning the power on
Abnormal if indoor controller board could not receive any signal normally for 3 minutes.
Consider the unit as abnormal under the following condition. When 2 or more indoor units are connected to an outdoor unit,
indoor controller board could not receive a signal for 3 minutes from outdoor controller circuit board, a signal which allows
outdoor controller circuit board to transmit signals.
3. Cause, check method and remedy
Note: Refer also to the Service Handbook for the indoor units.
7-8-22
Error Code [6841]
1. Error code definition
A control communication synchronism not recover
2. Error definition and error detection method
Indoor/outdoor unit communication error (Outdoor unit)
Abnormal if "0" receiving is detected 30 times continuously though outdoor controller circuit board has transmitted "1".
Abnormal if outdoor controller circuit board could not find blank of transmission path for 3 minutes.
3. Cause, check method and remedy
Note: Refer also to the Service Handbook for the indoor units.
Cause
Check method and remedy
(1)
Contact failure, short circuit or miswiring (converse wiring) of in-
door/outdoor unit connecting wire.
Check disconnecting or looseness of indoor
/outdoor unit connecting wire of indoor unit or
outdoor unit. Check all the units in case of
twin/triple/quadruple indoor unit system.
(2)
Defective transmitting receiving circuit of outdoor controller cir-
cuit board.
Turn the power off, and on again to check. If
abnormality generates again, replace indoor
controller board or outdoor controller circuit
board.
(3)
Defective transmitting receiving circuit of indoor controller board.
(4)
Noise has entered into indoor/outdoor unit connecting wire.
(5)
Defective fan motor
Turn the power off, and detach fan motor
from connector (CNF1, 2). Then turn the
power on again. If abnormality is not dis-
played, replace fan motor. If abnormality is
displayed, replace outdoor controller circuit
board.
(6)
Defective rush current resistor of outdoor power circuit board
Check the rush current resistor on outdoor
power circuit board with tester. If open is de-
tected, replace the power circuit board.
Cause
Check method and remedy
(1)
Indoor/outdoor unit connecting wire has contact failure.
Check disconnection or looseness of indoor/
outdoor unit connecting wire.
(2)
Defective communication circuit of outdoor controller circuit
board.
Turn the power off, and on again to check.
Replace outdoor controller circuit board if ab-
normality is displayed again.
(3)
Noise has entered power supply.
(4)
Noise has entered indoor/outdoor unit connecting wire.
0000004984.BOOK 79 ページ 2019年5月17日 金曜日 午前8時21分
Содержание City Multi CMH-WM250V-A
Страница 1: ......
Страница 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Страница 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Страница 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Страница 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Страница 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Страница 147: ... 5 3 Hydro Unit Control 28 chapter 5 BS_05_E 5 Control 0000004980 BOOK 28 ページ 2019年5月9日 木曜日 午後6時18分 ...
Страница 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Страница 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Страница 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Страница 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Страница 436: ......