[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
BS_07_E
chapter 7 -
45
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-6-26
Error Codes [4250, 4255, 4256] Detail Code 104
1. Error code definition
Short-circuited IPM/Ground fault (Detail code 104)
2. Error definition and error detection method
When IPM/IGBT short damage or grounding on the load side is detected just before starting the inverter.
3. Cause, check method and remedy
In the case of 4250
In the case of 4255 and 4256
Hydro unit
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems]
Cause
Check method and remedy
(1)
Grounding fault compressor
Refer to the following page(s).
[8-10-3 Checking the Compressor for Ground Fault and Coil Resistance
Problems]
(2)
Inverter output related
Refer to the following page(s).
[8-10-2 Checking the Inverter Board Error Detection Circuit]
[8-10-3 Checking the Compressor for Ground Fault and Coil Resistance
Problems]
[8-10-4 Checking the Inverter for Damage at No-Load]
[8-10-5 Checking the Inverter for Damage during Compressor Opera-
tion]
[8-10-15 Checking the Installation Conditions]
Cause
Check method and remedy
(1)
Grounding fault of fan motor
Refer to the following page(s).
[8-10-7 Checking the Fan Motor for Ground Fault and Coil Resistance
Problems]
(2)
Fan board failure
Refer to the following page(s).
[8-10-8 Checking the Fan Board Error Detection Circuit at No Load]
[8-10-9 Checking the Fan Board for Damage at No Load]
[8-10-10 Checking the Fan Board for Damage with Load]
Cause
Check method and remedy
(1)
Grounding fault of the pump
Refer to the following page(s).
[8-10-11 Checking the Pump Motor for Ground Fault and Coil Resis-
tance Problems]
(2)
Inverter output related
Refer to the following page(s).
[8-10-2 Checking the Inverter Board Error Detection Circuit]
[8-10-11 Checking the Pump Motor for Ground Fault and Coil Resis-
tance Problems]
[8-10-13 Checking the Pump INV Board for Damage (Without load)]
[8-10-14 Checking the Pump INV Board for Damage (During pump op-
eration)]
[8-10-15 Checking the Installation Conditions]
0000004984.BOOK 45 ページ 2019年5月17日 金曜日 午前8時21分
Содержание City Multi CMH-WM250V-A
Страница 1: ......
Страница 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Страница 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Страница 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Страница 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Страница 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Страница 147: ... 5 3 Hydro Unit Control 28 chapter 5 BS_05_E 5 Control 0000004980 BOOK 28 ページ 2019年5月9日 木曜日 午後6時18分 ...
Страница 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Страница 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Страница 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Страница 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Страница 436: ......