3. POSITIONING SIGNALS
3
−
44
(4) Manual pulse generator smoothing magnification setting area
(D752 to D754) ................................... Data from SCPU to PCPU
(a) These devices are used to set the smoothing time constants of manual
pulse generators.
Manual Pulse Generator Smoothing
Magnification Setting Register
Setting Range
Manual pulse generator 1 (P1) : D752
Manual pulse generator 2 (P2) : D753
Manual pulse generator 3 (P3) : D754
0 to 59
(b) When the smoothing magnification is set, the smoothing time constant is as
indicated by the following expression.
Smoothing time constant (t) = (smoothing magnifi 1)
×
56.8 [ms]
(c) Operation
V
t
t
t
t
V1
OFF
ON
Manual pulse
generator enable flag
(M2051)
Manual pulse
generator input
Output speed (V1) = (number of input pulses/ms)
×
(manual pulse
generator 1-pulse input magnification setting)
Travel value (L) = (travel value per pulse)
×
number of input pulses
×
(manual pulse generator 1-pulse input magnification
setting)
REMARKS
1) The travel value per pulse of the manual pulse generator is as indicated
below.
•
Setting unit
mm
: 0.1
µ
m
inch
: 0.00001inch
degree : 0.00001degree
PULSE : 1 PLS
2) The smoothing time constant is 56.8ms to 3408ms.