MANTENANCE
Calibrate the screen
If necessary, it is possible to calibrate the touchscreen.
1. Disconnect the power supply from the equipment.
2. Open the front door to access the HMI card.
3. Lower microswitch 8 on the HMI card to the OFF position.
4. Connect the power supply to the equipment and turn it on.
5. Follow the calibrating instructions which appear on the screen.
6. Disconnect the power supply from the equipment.
7. Raise microswitch 8 on the HMI card to the ON position.