USER MANUAL
Document reference MAODS301/E
SpeedSys300 ODS301 overspeed detection system
Edition 4 - May 2022
F - 14
Parameters and configuration settings
APPENDIX F: SPEEDSYS300 ODS301 MODBUS REGISTER DEFINITIONS
F.2.3 Device configuration – admin
describes the SpeedSys300 ODS301 Modbus registers related to the module
configuration – admin.
NOTE:
The Modbus registers in this data block are read/write.
Table F-7:
SpeedSys300 ODS301 Modbus registers – module configuration – user
Address
Name
Data
type
Range
Access
Description
2000
tag_1
char16
Level 0
2008
tag_2
char16
Level 0
2016
tag_3
char16
Level 0
2024
dev_comment
char32
Level 0
2040
modbus_addr
uint16
1 to 254
Level 0
Modbus address for RS-485 interface
2041
baud_rs485
uint16
0 to 5
Level 0
Coded baud rate for RS-485 interface:
0 – 4800
1 – 9600
2 – 19200
3 – 38400
4 – 57600
5 – 115200.
2042
Reserved
uint16
Level 0
2043
parity_rs485
uint16
0 to 2
Level 0
0 – no parity, 1 – even parity, 2 – odd parity
2044
rs485_term
uint16
0 to 1
Level 0
0 – RS-485 termination off, 1 – on
2045
crc_dev_user
uint16
Level 0
Parameter block CRC
Table F-8:
SpeedSys300 ODS301 Modbus registers – module configuration – admin
Address
Name
Data
type
Range
Access
Description
2500
tag_1_adm
char16
Level 1
2508
tag_2_adm
char16
Level 1
2516
tag_3_adm
char16
Level 1
2524
dev_comment_adm
char32
Level 1
2540
voting_struct
uint16
Level 1
Voting structure - only for reporting.
(For information only.)
2541
crc_dev_adm
uint16
Level 1
Parameter block CRC