Document reference MAODS301/E
USER MANUAL
Edition 4 - May 2022
SpeedSys300 ODS301 overspeed detection system
3 - 13
Installation considerations
INSTALLATION OF A SPEEDSYS300 ODS301
and
illustrate the two different ways in which a 2oo2 voting logic
structure can be implemented using the safety relay 2 of two SpeedSys300 ODS301
modules.
3.2.5.3
2oo3 voting
With a 2oo3 voting logic structure, three devices/relays are connected in combination such
that a 2oo3 signal is given if two out of three devices switch their relays (see
).
Table 3-9:
2oo2 – using safety relay 2 of SpeedSys300 ODS301 modules (1)
SpeedSys300 ODS301
modules
2oo2 to customer
#1
#2
B21
↔
B21
↔
2oo2 connection to customer circuit
B22
↔
B22
↔
2oo2 connection to customer circuit
Table 3-10:
2oo2 – using safety relay 2 of SpeedSys300 ODS301 modules (2)
SpeedSys300 ODS301
modules
2oo2 to customer
#1
#2
B23
↔
B23
↔
2oo2 connection to customer circuit
B24
↔
B24
↔
2oo2 connection to customer circuit
Figure 3-6:
2oo3 voting – relay connections
2oo3
Module #1
Relay A
Module #2
Relay B
Module #2
Relay B
Module #3
Relay C
Module #3
Relay C
Module #1
Relay A