USER MANUAL
Document reference MAODS301/E
SpeedSys300 ODS301 overspeed detection system
Edition 4 - May 2022
F - 24
Parameters and configuration settings
APPENDIX F: SPEEDSYS300 ODS301 MODBUS REGISTER DEFINITIONS
5536
r1_del_acc_max
uint32
0 to 1000000
Level 1
Relay 1 delay for max. acceleration alarm.
Unit: 1 ms.
5538
r2_del_acc_max
uint32
0 to 1000000
Level 1
Relay 2 delay for max. acceleration alarm.
Unit: 1 ms.
5540
r3_del_acc_max
uint32
0 to 1000000
Level 1
Relay 3 delay for max. acceleration alarm.
Unit: 1 ms.
5542
r4_del_acc_max
uint32
0 to 1000000
Level 1
Relay 4 delay for max. acceleration alarm.
Unit: 1 ms.
5544
do_del_acc_max
uint32
0 to 1000000
Level 1
Digital out delay for max. acceleration alarm.
Unit: 1 ms.
5546
r1_del_acc_min
uint32
0 to 1000000
Level 1
Relay 1 delay for min. acceleration alarm.
Unit: 1 ms.
5548
r2_del_acc_min
uint32
0 to 1000000
Level 1
Relay 2 delay for min. acceleration alarm.
Unit: 1 ms.
5550
r3_del_acc_min
uint32
0 to 1000000
Level 1
Relay 3 delay for min. acceleration alarm.
Unit: 1 ms.
5552
r4_del_acc_min
uint32
0 to 1000000
Level 1
Relay 4 delay for min. acceleration alarm.
Unit: 1 ms.
5554
do_del_acc_min
uint32
0 to 1000000
Level 1
Digital out delay for min. acceleration alarm.
Unit: 1 ms.
5556
r1_sp_max
single
v_min to
v_max
Level 1
Relay 1 overspeed alarm value.
Range defined in ‘Output config - factory’.
5558
r2_sp_max
single
v_min to
v_max
Level 1
Relay 2 overspeed alarm value.
Range defined in ‘Output config - factory’.
5560
r3_sp_max
single
v_min to
v_max
Level 1
Relay 3 overspeed alarm value.
Range defined in ‘Output config - factory’.
5562
r4_sp_max
single
v_min to
v_max
Level 1
Relay 4 overspeed alarm value.
Range defined in ‘Output config - factory’.
5564
do_sp_max
single
v_min to
v_max
Level 1
Digital out overspeed alarm value.
Range defined in ‘Output config - factory’.
5566
r1_sp_min
single
v_min to
v_max
Level 1
Relay 1 underspeed alarm value.
Range defined in ‘Output config - factory’.
5568
r2_sp_min
single
v_min to
v_max
Level 1
Relay 2 underspeed alarm value.
Range defined in ‘Output config - factory’.
5570
r3_sp_min
single
v_min to
v_max
Level 1
Relay 3 underspeed alarm value.
Range defined in ‘Output config - factory’.
5572
r4_sp_min
single
v_min to
v_max
Level 1
Relay 4 underspeed alarm value.
Range defined in ‘Output config - factory’.
5574
do_sp_min
single
v_min to
v_max
Level 1
Digital out underspeed alarm value.
Range defined in ‘Output config - factory’.
Table F-13:
SpeedSys300 ODS301 Modbus registers – output configuration – admin (continued)
Address
Name
Data
type
Range
Access
Description