Installation considerations
INSTALLATION OF A SPEEDSYS300 ODS301
Table 3-2:
Shielding requirements/specifications for SpeedSys300 ODS301
in an EMC/ESD uncontrolled environment
SpeedSys300 ODS301 shielding requirements
(EMC/ESD uncontrolled environment)
Connector
Cable
Shielding
Label
Description
Max. length
Type
Required
Near side
(module
end)
Far side
(other
end)
Sensor / input channel
2-WIRE
VOLTAGE
Magnetic
(variable reluctance)
sensor
30 m.
See Note 1.
Shielded
2-wire
twisted-pair
(≥0.5 mm
2
)
Yes
Yes
No
3-WIRE
VOLTAGE
Electronic sensor
300 m
No
2-WIRE
CURRENT
Proximity sensor
(current loop)
1000 m.
See Note 2.
Yes.
See Note 3
Other
SAFETY ANALOG /
FREQ OUT
---
30 m
Shielded
2-wire
Yes
Yes
No
POWER
PSU 1
---
10 m
Shielded
2-wire
No
POWER
PSU 2
---
10 m
Shielded
2-wire
No
RELAY 3 /
RELAY 4
---
30 m
Shielded
2-wire
Yes.
See Note 4
SAFETY
RELAY 1
---
30 m
Shielded
2-wire
Yes.
See Note 4
SAFETY
RELAY 2
---
30 m
Shielded
2-wire
Yes.
See Note 4
PROOF TEST IN /
BINARY OUT
---
30 m
Shielded
2-wire
Yes.
See Note 4
MODBUS
RS485
---
30 m
Shielded
2-wire
Yes.
See Note 4
Notes
1. For a magnetic (variable reluctance) sensor, the maximum cable length depends on the sensor impedance, cable impedance, cable
routing and monitoring system (instrument) input impedance, and can vary from 10 to 500 m.
2. A TQ9xx-based measurement chain using an IQS900 configured with a current output and a GSI127 galvanic separation unit, allows
transmission over distances up to 1 km – longer than any other solution.
3. For applications in potentially explosive atmospheres (Ex Zones), the area can be considered as an EMC/ESD controlled environment so
the shield at the far end (other/sensor side) is not required.
4. For shielded EMC cabinets (cubicles), the inside of the cabinet can be considered as EMC/ESD controlled environment so shielding for the
wiring (cabling and connections) inside of the cabinet is not required, except for the speed signals.
Содержание vibro-meter SpeedSys300 ODS301