Document reference MAODS301/E
USER MANUAL
Edition 4 - May 2022
SpeedSys300 ODS301 overspeed detection system
F - 17
Parameters and configuration settings
APPENDIX F: SPEEDSYS300 ODS301 MODBUS REGISTER DEFINITIONS
F.2.6 Diagnostics configuration – admin
describes the SpeedSys300 ODS301 Modbus registers related to the module
diagnostics configuration – admin.
NOTE:
The Modbus registers in this data block are read/write.
Table F-11:
SpeedSys300 ODS301 Modbus registers – diagnostics configuration – admin
Address
Name
Data
type
Range
Access
Description
4500
bad_pulse_cnt
uint32
bp_tout_min
to
bp_tout_max
Level 1
Count-out for bad pulses:
Min. count of good pulses per one bad pulse.
Value 0 causes each bad pulse to
immediately raise a diagnostic error.
Range defined in ‘Diag config - factory’
4502
max_sens_I
single
i_sens_min to
i_sens_max
Level 1
Max. sensor current Range defined in
‘Diag config - factory’
4504
min_sens_I
single
i_sens_min to
i_sens_max
Level 1
Min. sensor current Range defined in
‘Diag config - factory’
4506
max_sens_u
single
v_sens_min to
v_sens_max
Level 1
Max. sensor voltage Range defined in
‘Diag config - factory’
4508
min_sens_u
single
v_sens_min to
v_sens_max
Level 1
Min. sensor voltage Range defined in
‘Diag config - factory’
4510
aout_chk
single
aout_chk_min
to
aout_chk_max
Level 1
Analog output readback difference [mA]
Range defined in ‘Diag config - factory’
Содержание vibro-meter SpeedSys300 ODS301