USER MANUAL

Document reference MAODS301/E

SpeedSys300 ODS301 overspeed detection system

Edition 4 - May 2022

4 - 4

Getting started

CONFIGURATION OF A SPEEDSYS300 ODS301

4-

In  the  SpeedSys300  software,  configure  the  USB  communications  interface  between
SpeedSys300 software and the SpeedSys300 ODS301 module.
Click  the 

Settings > Interface settings

  menu  and  use  the  Interface settings  window

that is displayed to configure the communications interface (see

Figure 4-2

).

Use Serial port to select the COM port to use for USB communications with the module.
The available COM ports are automatically detected when the software starts and can
be manually detected using the Rescan control.
Ensure  that  the  USB Connection  control  is  selected  as  this  is  always  required  to
communicate with a SpeedSys300 ODS301 module via USB.
(Baud rate,  Parity  and  Modbus address  are  reserved  for  serial  communications  /
factory use.)

5-

When configured, click OK to continue.

NOTE:

If required, Windows Device Manager can be used to find the COM port number to
use.
For  example,  start  the  Device Manager  and  in  the  main  window,  under
Ports (COM & LPT), look for USB serial port (COM

x

).

If  the  SpeedSys300  ODS301  module  is  connected  after  the  SpeedSys300
software was started, then the Rescan control in the Interface settings window may
need to be used in order to see the module as a COM

x

 port.

Once  communications  is  established,  the  SpeedSys300  software  communicates
automatically with the SpeedSys300 ODS301 module to obtain high-level module information
that is displayed in the overall module information and controls window (right):

PC interface – computer interface port and settings being used.
For example, COM4 (USB).

Access level – user access level (permissions).
For example, User, when first connected to a module.

Device status – operating mode/status of the module.
For example, Operating, during normal operation of a module.

Serial number – unique factory-assigned serial identification number for the module.
For example, SSY300-

xxxxx

.

Tag number – user-configurable tag number used to identify the module.

Figure 4-2:

SpeedSys300 user interface – Interface settings

Содержание vibro-meter SpeedSys300 ODS301

Страница 1: ...www meggittsensing com energy www meggitt com USER MANUAL Title page SpeedSys300 ODS301 overspeed detection system ODS This document contains important information about products that are intended for...

Страница 2: ...ommunications interface to use instrument earth GND IE See Figure 1 2 Table 2 7 Table 2 8 and Table 2 13 Updated 3 2 2 Power supply and 3 2 3 Grounding and added 3 2 4 Shielding in order to clarify po...

Страница 3: ...clude two new FAQs See D 7 I am seeing a Slave communication error message What should I check and D 8 I am seeing a Relays PST failed message What should I check PW 4 09 05 2022 Peter Ward Updated 7...

Страница 4: ...Meggitt SA publication nor for any statements contained in extracts summaries translations or any other documents not authored and produced by Meggitt SA The certifications and warranties applicable t...

Страница 5: ...rmerly Vibro Meter SA vibro meter is a product line of Meggitt that applies our core sensing and monitoring technologies to power generation oil gas and other industrial markets Meggitt SA produces a...

Страница 6: ...hem to design install configure use and or maintain such systems correctly and safely Adhere to the instructions The procedures described in this manual should be strictly adhered to in order to ensur...

Страница 7: ...n system ODS should also refer to the following document SpeedSys300 ODS301 overspeed detection system safety manual document reference MAODS301 FS E NOTE To ensure that the latest version of document...

Страница 8: ...USER MANUAL Document reference MAODS301 E SpeedSys300 ODS301 overspeed detection system Edition 4 May 2022 viii THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 9: ...ND OR THIRD PARTIES AND OR RESULT IN DAMAGE TO EQUIPMENT The CAUTION safety symbol This draws the operator s attention to information directives or procedures which must be executed or followed Failur...

Страница 10: ...CT TO SPECIFIC CONDITIONS OF USE SPECIAL CONDITIONS FOR SAFE USE WHICH ARE SPECIFIED IN THE CERTIFICATE A U PLACED AFTER AN EX CERTIFICATE NUMBER IS USED TO INDICATE COMPONENTS THAT ARE SUBJECT TO A S...

Страница 11: ...ropriate data sheet See also the Handling precautions for electrostatic sensitive devices on page xii WHEN INSTALLING A SPEEDSYS300 ODS301 OVERSPEED DETECTION SYSTEM ODS OBSERVE ALL SAFETY WARNING AND...

Страница 12: ...ess it is absolutely necessary Only hold modules cards by their handles or panels Do not touch printed circuit boards their connectors or their components with conductive devices or with your hands Pu...

Страница 13: ...1 System overview 1 1 1 1 1 Introduction 1 1 1 1 2 SIL safety 1 4 1 1 3 Safety related and non safety related functionality 1 4 1 1 4 Software 1 5 1 2 Applications information 1 5 1 2 1 Applications...

Страница 14: ...erfaces 3 18 3 2 10 General wiring diagram 3 19 3 2 11 Safety instructions safety related applications 3 20 3 2 12 Safety instructions potentially explosive atmospheres 3 20 3 2 12 1 Category 1 G equi...

Страница 15: ...t tab Measurement 5 4 5 3 2 Measurement tab Advanced settings 5 5 5 4 Output tab 5 7 5 4 1 Output tab Digital outputs 5 7 5 4 2 Output tab Analog output 5 9 5 5 Diagnostics tab 5 10 5 5 1 Diagnostics...

Страница 16: ...ICATIONS C 1 D APPENDIX D FREQUENTLY ASKED QUESTIONS FAQ D 1 D 1 The SpeedSys300 software cannot communicate with my SpeedSys300 ODS301 module What do I need to check D 1 D 2 How do I use a Meggitt vi...

Страница 17: ...F 1 F 1 2 Control F 4 F 1 3 Current values F 5 F 1 4 Diagnostics data F 8 F 1 5 Slave communication status F 11 F 2 Parameters and configuration settings F 13 F 2 1 Admin password F 13 F 2 2 Device c...

Страница 18: ...USER MANUAL Document reference MAODS301 E SpeedSys300 ODS301 overspeed detection system Edition 4 May 2022 xviii THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 19: ...1 1 Introduction The SpeedSys300 ODS301 overspeed detection system ODS system is an overspeed detection and protection system with additional monitoring from Meggitt s vibro meter product line It is...

Страница 20: ...eed and acceleration measurements against the configured alarm limits and will activate the safety relays relay 1 and relay 2 and additional non safety relays relay 3 and relay 4 should a measurement...

Страница 21: ...terface RS 485 USB for communications with the SpeedSys300 software Analog output 4 to 20 mA Frequency speed output Safety relay 1 relay 1 Safety relay 2 relay 2 Additional relay 3 relay 3 Additional...

Страница 22: ...n be used to indicate when a measurement exceeds a non critical limit or to communicate module status information as configured using the application software A digital frequency speed output is avail...

Страница 23: ...the VM600Mk2 VM600 and VibroSmart machinery monitoring systems As the safety critical speed system SpeedSys300 ODS301 overspeed detection system and any other systems vibration and or combustion are c...

Страница 24: ...removable screw terminal connectors USB Type A to USB Mini B cable for computer to SpeedSys300 ODS301 module communications SpeedSys300 software available via FTP NOTE Refer to the SpeedSys300 ODS301...

Страница 25: ...e module s second safety relay SAFETY RELAY 2 Table 2 1 provides detailed information on the behaviour of the SpeedSys300 ODS301 module s Power and Error LEDs Table 2 1 Behaviour of SpeedSys300 ODS301...

Страница 26: ...oes not provide information on the operating status of the module such as overspeed underspeed and or acceleration alarms Table 2 2 provides detailed information on the behaviour of the SpeedSys300 OD...

Страница 27: ...on to different types of speed sensor measurement chain but only one measurement channel can be configured and used by the module at any one time 8 connectors on the bottom of the module for all other...

Страница 28: ...ference MAODS301 E SpeedSys300 ODS301 overspeed detection system Edition 4 May 2022 2 4 SpeedSys300 ODS301 module connectors OVERVIEW OF THE SPEEDSYS300 ODS301 MODULE HARDWARE Figure 2 1 SpeedSys300 O...

Страница 29: ...MODULE HARDWARE Figure 2 2 shows the relationship between the connector information on the front panel of the SpeedSys300 ODS301 module and the actual positions of the connectors on the top of the mo...

Страница 30: ...2022 2 6 SpeedSys300 ODS301 module connectors OVERVIEW OF THE SPEEDSYS300 ODS301 MODULE HARDWARE Figure 2 3 shows the relationship between the connectors on the top of the module and their pinouts as...

Страница 31: ...01 MODULE HARDWARE Figure 2 4 shows the relationship between the connector information on the front panel of the SpeedSys300 ODS301 module and the actual positions of the connectors on the bottom of t...

Страница 32: ...2 2 8 SpeedSys300 ODS301 module connectors OVERVIEW OF THE SPEEDSYS300 ODS301 MODULE HARDWARE Figure 2 5 shows the relationship between the connectors on the bottom of the module and their pinouts as...

Страница 33: ...onal GND ground I input Table 2 4 SpeedSys300 ODS301 module 3 WIRE VOLTAGE connector pinouts SpeedSys300 ODS301 3 WIRE VOLTAGE connector Label Pin Name function Direction Definition 3 WIRE VOLTAGE B05...

Страница 34: ...20 mA current output A15 FREQ O Frequency output Signal A16 FREQ B Frequency output GND Notes B bidirectional GND ground O output Table 2 7 SpeedSys300 ODS301 module POWER PSU 1 connector pinouts Spee...

Страница 35: ...module SAFETY RELAY 1 connector pinouts SpeedSys300 ODS301 SAFETY RELAY 1 connector Label Pin Name function Direction Definition SAFETY RELAY 1 B17 NO1 B Safety relay 1 Normally open NO contact 1 B18...

Страница 36: ...Proof test input GND Reference signal C15 OUT O Binary output Status signal C16 GND G Binary output GND Reference signal Notes G ground I input O output GND signal ground Table 2 13 SpeedSys300 ODS30...

Страница 37: ...n the body of a SpeedSys300 ODS301 module 1 Ensure that the raised tab on the front of the screw terminal connector is pushed down flat so that the rear of the connector is not obstructed 2 Align the...

Страница 38: ...ent reference MAODS301 E SpeedSys300 ODS301 overspeed detection system Edition 4 May 2022 2 14 SpeedSys300 ODS301 module connectors OVERVIEW OF THE SPEEDSYS300 ODS301 MODULE HARDWARE THIS PAGE INTENTI...

Страница 39: ...Knowledge of the installation of field wiring and protective earth PE instrument earth IE and intrinsically safe earth IS is also required 3 1 Module details As shown in Figure 2 1 the front panel of...

Страница 40: ...ough the vents on the top of the module When SpeedSys300 ODS301 modules are installed in an industrial housing cabinet or other suitable enclosure in which natural ventilation is used a space of at le...

Страница 41: ...peedSys300 ODS301 module s power supply input NOTE Refer to the SpeedSys300 ODS301 overspeed detection system data sheet for further information The SpeedSys300 ODS301 module has two separate 24 VDC p...

Страница 42: ...nding on the application For all applications one instrument earth GND IE terminal per module needs to be connected to the system instrument earth IE ground For ordinary applications non explosive atm...

Страница 43: ...sically safe earth GND IS For applications using a 2 wire voltage sensor magnetic sensor the SpeedSys300 ODS301 module requires an installation in a controlled electromagnetic EMC environment with the...

Страница 44: ...hielded 2 wire Yes See Note 4 SAFETY RELAY 1 30 m Shielded 2 wire Yes See Note 4 SAFETY RELAY 2 30 m Shielded 2 wire Yes See Note 4 PROOF TEST IN BINARY OUT 30 m Shielded 2 wire Yes See Note 4 MODBUS...

Страница 45: ...ne For example a SIL 3 overspeed solution for gas turbines uses 3 SpeedSys300 ODS301 modules configured with external 2oo3 voting logic It is important to note that hardwiring the voting logic structu...

Страница 46: ...ting logic structure two devices relays are connected in series such that a 1oo2 signal is given if one of the devices switches its relay see Figure 3 2 Accordingly to obtain a 1oo2 voting logic struc...

Страница 47: ...e pole single throw DPST relays there are several ways in which two modules can be hardwired in series to obtain a 1oo2 voting logic structure Table 3 3 and Table 3 4 illustrate the two different ways...

Страница 48: ...lay 1 of SpeedSys300 ODS301 modules 2 SpeedSys300 ODS301 modules 1oo2 to customer 1 2 B19 1oo2 connection to customer circuit B20 B19 B20 1oo2 connection to customer circuit Table 3 5 1oo2 using safet...

Страница 49: ...oting logic structure two devices relays are connected in parallel such that a 2oo2 signal is given if both devices switch their relays see Figure 3 4 Accordingly to obtain a 2oo2 voting logic structu...

Страница 50: ...l to obtain a 2oo2 voting logic structure Table 3 7 and Table 3 8 illustrate the two different ways in which a 2oo2 voting logic structure can be implemented using the safety relay 1 of two SpeedSys30...

Страница 51: ...on such that a 2oo3 signal is given if two out of three devices switch their relays see Figure 3 6 Table 3 9 2oo2 using safety relay 2 of SpeedSys300 ODS301 modules 1 SpeedSys300 ODS301 modules 2oo2 t...

Страница 52: ...ture Because a SpeedSys300 ODS301 module s safety relays relay 1 and relay 2 are double pole single throw DPST relays there are several ways in which three modules can be hardwired in combination to o...

Страница 53: ...3 12 illustrates the way in which a 2oo3 voting logic structure can be implemented using the safety relay 2 of three SpeedSys300 ODS301 modules Table 3 12 2oo3 using safety relay 2 of SpeedSys300 ODS...

Страница 54: ...an EMC ESD uncontrolled area is shown in 3 2 10 General wiring diagram 3 2 7 Installations in hazardous areas NOTE Knowledge of the installation of field wiring and protective earth PE instrument ear...

Страница 55: ...all observed See also 3 2 3 Grounding 3 2 8 Sensor input channel interface circuitry and 3 2 12 Safety instructions potentially explosive atmospheres 3 2 8 Sensor input channel interface circuitry The...

Страница 56: ...acts of the 2 WIRE VOLTAGE connector see Table 2 3 In case of the 2 wire voltage magnetic sensor not being used the bridge must be removed in order to ensure full functionality of the module Refer to...

Страница 57: ...tions INSTALLATION OF A SPEEDSYS300 ODS301 3 2 10 General wiring diagram Figure 3 9 shows a general wiring diagram for the SpeedSys300 ODS301 module illustrating the grounding and shielding required f...

Страница 58: ...ontrollers that mutually monitor each other the Duotec system For all information and installation instructions concerning applications functional safety contexts refer to the SpeedSys300 ODS301 overs...

Страница 59: ...LE IS CONNECTED TO CIRCUITS ENTERING A POTENTIALLY EXPLOSIVE AREA THE GENERAL INSTALLATION REGULATIONS FOR EXPLOSION PROTECTION EN 60079 14 THE APPLICABLE SAFETY DIRECTIVES AND THE INSTRUCTIONS OF THI...

Страница 60: ...rail mounting adaptor bottom thereby compressing the springs while pivoting the module in order to hook the opposite end of the mounting adaptor over the other edge of the DIN rail bottom 3 3 1 2 Remo...

Страница 61: ...ating systems such as Windows 10 Windows 8 1 or Windows 7 NOTE Windows 7 is not recommended for new installations as Microsoft support for Windows 7 ended in January 2020 USB port with USB Type A conn...

Страница 62: ...Figure 4 1 and Figure 4 3 Looking from top to bottom and left to right the SpeedSys300 user interface consists of a title bar a menu bar a series of tabbed windows left and an overall module informat...

Страница 63: ...ION OF A SPEEDSYS300 ODS301 Note that in Figure 4 1 the overall module information and controls window right does not display any useful information for the module as the USB communications is not yet...

Страница 64: ...ed Windows Device Manager can be used to find the COM port number to use For example start the Device Manager and in the main window under Ports COM LPT look for USB serial port COMx If the SpeedSys30...

Страница 65: ...verall module information and controls window right now displays useful information for the module such as Access level User and Device status Operating Once communications has been established betwee...

Страница 66: ...ent from the configuration currently displayed by the SpeedSys300 software the user will be prompted to continue before the settings in the software are overwritten and displayed 4 5 2 Loading and sav...

Страница 67: ...of access levels to control and limit the functionality of the module software that are available to different users with different access levels There are two categories of access level user as foll...

Страница 68: ...ith Access level User 4 6 1 Changing the Admin access level password For improved security especially in deployed SpeedSys300 ODS301 overspeed detection systems it is strongly recommend to change the...

Страница 69: ...rd More specifically the module is completely reconfigured using all of the parameters configured changed in the SpeedSys300 software so it is important that the password is the only parameter that ha...

Страница 70: ...MANUAL Document reference MAODS301 E SpeedSys300 ODS301 overspeed detection system Edition 4 May 2022 4 10 Access levels permissions CONFIGURATION OF A SPEEDSYS300 ODS301 THIS PAGE INTENTIONALLY LEFT...

Страница 71: ...parameters and settings required for the application then software must be used to upload program the configuration to the module NOTE When developing configurations for SpeedSys300 ODS301 modules the...

Страница 72: ...re basic configuration information for a SpeedSys300 ODS301 module such as tag names and comments descriptive text That is User access level information In addition the MODBUS fields parameters are us...

Страница 73: ...ration admin the data entry fields descriptive text must be completed correctly in order to create an IEC 61511 compliant report for the SpeedSys300 ODS301 module This is typically required for the us...

Страница 74: ...achine s axis Selecting Radial switches to measuring perpendicular to the machine s axis Tangential means measuring the axis under a certain angle Speed sensing surface Four options for the speed sens...

Страница 75: ...mVRMS to 80 VRMS Trigger level current voltage Configures the pulse detection threshold for the input signal current or voltage Above the threshold a signal is assumed to be a pulse For current senso...

Страница 76: ...n 1 and 5000 The acceleration is calculated by dividing a frequency difference by the time that has passed The difference is calculated from averaged frequencies see the image below The time between t...

Страница 77: ...eneral each relay and the digital output can be configured individually However it is important to note that for the safety relays Relay 1 and Relay 2 certain configuration parameters are restricted M...

Страница 78: ...tial trip signal Diagnostics safe state Allows the system diagnostics to cause a trip signal Trip events are listed on the Diagnostics tab NOTE For safety relay 1 and safety relay 2 Diagnostics safe s...

Страница 79: ...ame Acceleration cut in speed Define this parameter to set the minimal speed for which acceleration alarms are indicated Below this speed no acceleration alarms are evaluated 5 4 2 Output tab Analog o...

Страница 80: ...d sensor type see 5 3 Measurement tab For example for applications using a TQxxx IQSxxx proximity measurement chain as the sensor input Sensor type 2 wire current the recommended Sensor OK current ran...

Страница 81: ...ue of 0 25 mA or higher NOTE Versions of the SpeedSys300 software with language pack file version 1 13 or later for example language_eng_1 13_Meggitt lngpack use updated Analog output readback differe...

Страница 82: ...g output including the minimum and maximum values that are stored for speed and acceleration Test and reset on The Test and reset on off button command is used to activate deactivate the Test and rese...

Страница 83: ...he current state status of the digital outputs relays and digital 5 6 3 Process tab Speed plot The speed measurement history is shown in a Speed plot at the bottom of the window using an x axis that i...

Страница 84: ...peedSys300 ODS301 module s hardware For example the user can observe the overall supply voltage and temperature CPU for the module as well as individual voltages and currents for the individual redund...

Страница 85: ...Past errors are stored in the error memory to give the user the ability to identify potential problems risks that are caused by short term malfunctions or that remain undetected due to the short dura...

Страница 86: ...a PDF report file NOTE PDF reports generated in this way contain human readable configuration information pdf that is equivalent to the computer readable configuration information stored in a SpeedSys...

Страница 87: ...ma separated values file csv for data sharing and or offline analysis The timestamps Time displayed in the Event log table are calculated using the current time of the connected computer running the S...

Страница 88: ...the mouse pointer mouse over an error in the Event log table left will highlight the associated errors in the Error codes summary right For further information on each error code see Appendix E Speed...

Страница 89: ...ule information and controls window right updates to display Device status Programming safe state 3 In the overall module information and controls window right click the Program device settings button...

Страница 90: ...MANUAL Document reference MAODS301 E SpeedSys300 ODS301 overspeed detection system Edition 4 May 2022 5 20 Programming parameters COMMISSIONING OF A SPEEDSYS300 ODS301 THIS PAGE INTENTIONALLY LEFT BL...

Страница 91: ...RTU interface are Modbus address 1 slave Modbus transmission speed 19200 baud rate Number of data bits 8 Number of stop bits 1 Modbus parity check None Modbus line termination Inactive All of these c...

Страница 92: ...communication the SpeedSys300 ODS301 module is the Modbus server slave that responds to external transaction requests from client equipment such as a computer or DCS Modbus is a request response proto...

Страница 93: ...protocol can be used with half duplex or full duplex serial interfaces however the SpeedSys300 ODS301 module s interface supports half duplex 2 wire only The default SpeedSys300 ODS301 module communic...

Страница 94: ...Document reference MAODS301 E SpeedSys300 ODS301 overspeed detection system Edition 4 May 2022 6 4 Modbus register definitions MODBUS COMMUNICATIONS WITH A SPEEDSYS300 ODS301 THIS PAGE INTENTIONALLY...

Страница 95: ...M DEPENDS ON THE ATEX IECEX ZONE IN WHICH THE PRODUCT IS INSTALLED FOR EXAMPLE THE WIRING DIAGRAMS FIGURE 7 1 AND FIGURE 7 2 IN THIS SECTION ILLUSTRATE A TYPICAL SPEEDSYS300 ODS301 OVERSPEED DETECTION...

Страница 96: ...the input TQ9xx proximity probe with integral cable and or EA90x extension cable IQS9xx signal conditioner in an ABA17x industrial housing transmission cabling SpeedSys300 ODS301 module and optional...

Страница 97: ...T U 4g bcP SPaSb 40 gg fXcW TcP XR _a cTRcX b TTeT 40 gg C gg a gX Xch _a QT fXcW X cTVaP RPQ T 0 5 a E RdQXRP bd__ h PX aX RX_P fTa Sd T fTa X T 0 5 a E RdQXRP bd__ h 1PRZd_ 0dgX XPah fTa Sd T fTa X...

Страница 98: ...ca XR bT b a fXaT e cPVT a gX Xch bT b a fXaT RdaaT c E E 1A 1A B86 E 8B E 8 8B 8B 8 40 RPQ T Xb dc U bR _T U 4g bcP SPaSb 40 gg fXcW TcP XR _a cTRcX b TTeT 40 gg C gg a gX Xch _a QT fXcW X cTVaP RPQ...

Страница 99: ...a dry cloth only Keep away from live electrical parts Do not use any solvents or cleaning agents Never pour or spray any cleaner or liquid on the module WHERE MAINTENANCE IS REQUIRED IT MUST BE PERFOR...

Страница 100: ...USER MANUAL Document reference MAODS301 E SpeedSys300 ODS301 overspeed detection system Edition 4 May 2022 8 2 Cleaning MAINTENANCE THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 101: ...electronic equipment should be collected separately and then treated and disposed of in accordance with the best available and environmentally friendly techniques This is because electronic waste or e...

Страница 102: ...additional end of life product disposal information and guidance contact your local Meggitt representative Alternatively contact our main office Environment health and safety department Meggitt SA Ro...

Страница 103: ...Fribourg Switzerland Telephone 41 26 407 11 11 Email energysupport ch meggitt com Website www meggittsensing com energy 10 2Technical support Meggitt s technical support team provide both pre sales an...

Страница 104: ...10 2 Customer feedback SERVICE AND SUPPORT 10 4Customer feedback As part of our continuing commitment to improving customer service we warmly welcome your opinions To provide feedback complete the En...

Страница 105: ...ailed by return Received forms are typically processed and the RMA document sent within 2 working days NOTE Please do not return any products to Meggitt Switzerland without a supporting return merchan...

Страница 106: ...ct information First name Last name Job title Company Address Country Email Telephone Fax Product information Product type Part number PNR Serial number SER Note Enter Unknown if the serial number SER...

Страница 107: ...as the operating time before the problem Continuous Intermittent Temperature dependent Description of problem Please provide a detailed description in order to help with problem diagnosis If the reaso...

Страница 108: ...roduct information additional information required for SIL products only Note For SIL products used in functional safety contexts systems this SIL product information section must be completed When wa...

Страница 109: ...ition 4 May 2022 SpeedSys300 ODS301 overspeed detection system 10 7 Customer feedback SERVICE AND SUPPORT How long was the operating time before failure in hours Additional information A faulty indica...

Страница 110: ...ack SERVICE AND SUPPORT FEEDBACK Energy customer feedback form Manual information Title of manual SpeedSys300 ODS301 overspeed detection system ODS user manual Reference MAODS301 E Version Edition 4 D...

Страница 111: ...instructions clear and complete Yes No Are the descriptions easy to understand Yes No Are the examples and diagrams photos helpful Yes No Are there enough examples and diagrams photos Yes No Is the s...

Страница 112: ...USER MANUAL Document reference MAODS301 E SpeedSys300 ODS301 overspeed detection system Edition 4 May 2022 10 10 Customer feedback SERVICE AND SUPPORT THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 113: ...g 20 to 60 C 4 to 140 F Storage 40 to 85 C 40 to 185 F Humidity Operating 5 to 80 non condensing Storage 5 to 85 non condensing Safety Electrical safety Conforms to IEC EN 61010 1 Safety requirements...

Страница 114: ...USER MANUAL Document reference MAODS301 E SpeedSys300 ODS301 overspeed detection system Edition 4 May 2022 A 2 APPENDIX A ENVIRONMENTAL SPECIFICATIONS THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 115: ...Edition 4 May 2022 SpeedSys300 ODS301 overspeed detection system B 1 APPENDIX B ATEX CERTIFICATIONS APPENDIX B ATEX CERTIFICATIONS Table B 1 Related ATEX certificates Product s covered Certificate num...

Страница 116: ...USER MANUAL Document reference MAODS301 E SpeedSys300 ODS301 overspeed detection system Edition 4 May 2022 B 2 APPENDIX B ATEX CERTIFICATIONS THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 117: ...itt com EX CERTIFICATE ATEX Document reference IBExU 20 ATEX 1157 Edition 3 December 2021 Title page IBExU 20 ATEX 1157 for SpeedSys300 ODS301 overspeed detection system EX Note Although the Ex certif...

Страница 118: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 119: ...h Document reference IBExU 20 ATEX 1157 EX CERTIFICATE ATEX Edition 3 December 2021 IBExU 20 ATEX 1157 for SpeedSys300 ODS301 overspeed detection system 3 6 SpeedSys300 ODS301 FR IBExU 20 ATEX 1157 EN...

Страница 120: ...h EX CERTIFICATE ATEX Document reference IBExU 20 ATEX 1157 IBExU 20 ATEX 1157 for SpeedSys300 ODS301 overspeed detection system Edition 3 December 2021 4 6 SpeedSys300 ODS301 FR IBExU 20 ATEX 1157 EN...

Страница 121: ...an Document reference IBExU 20 ATEX 1157 EX CERTIFICATE ATEX Edition 3 December 2021 IBExU 20 ATEX 1157 for SpeedSys300 ODS301 overspeed detection system 5 6 SpeedSys300 ODS301 FR IBExU 20 ATEX 1157 E...

Страница 122: ...an EX CERTIFICATE ATEX Document reference IBExU 20 ATEX 1157 IBExU 20 ATEX 1157 for SpeedSys300 ODS301 overspeed detection system Edition 3 December 2021 6 6 SpeedSys300 ODS301 FR IBExU 20 ATEX 1157 E...

Страница 123: ...dition 4 May 2022 SpeedSys300 ODS301 overspeed detection system C 1 APPENDIX C IECEX CERTIFICATIONS APPENDIX C IECEx CERTIFICATIONS Table C 1 Related IECEx certificates Product s covered Certificate n...

Страница 124: ...USER MANUAL Document reference MAODS301 E SpeedSys300 ODS301 overspeed detection system Edition 4 May 2022 C 2 APPENDIX C IECEX CERTIFICATIONS THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 125: ...gitt com EX CERTIFICATE IECEx Document reference IECEx IBE 20 0045 Edition 2 December 2021 Title page IECEx IBE 20 0045 for SpeedSys300 ODS301 overspeed detection system EX Note Although the Ex certif...

Страница 126: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 127: ...safety i This Certificate does not indicate compliance with safety and performance requirements other than those expressly included in the Standards listed above TEST ASSESSMENT REPORTS A sample s of...

Страница 128: ...ertificate of Conformity Certificate No IECEx IBE 20 0045 Date of issue 2021 11 08 Page 3 of 4 Issue No 1 EQUIPMENT Equipment and systems covered by this Certificate are as follows SPECIFIC CONDITIONS...

Страница 129: ...ing voltage U N 30 V DC Switching current I N 2 A Switching power P 60 W Max voltage U m 220 V Non intrinsically safe USB circuit Rated voltage U N 5 V DC Rated current I N 63 mA Max voltage U m 125 V...

Страница 130: ...nal copy English EX CERTIFICATE IECEx Document reference IECEx IBE 20 0045 IECEx IBE 20 0045 for SpeedSys300 ODS301 overspeed detection system Edition 2 December 2021 6 6 THIS PAGE INTENTIONALLY LEFT...

Страница 131: ...on the computer running the SpeedSys300 software If the FT230X Basic UART is not available on the computer Windows typically reports this as a message when the USB cable to a powered SpeedSys300 ODS3...

Страница 132: ...SpeedSys300 software cannot communicate with my SpeedSys300 ODS301 APPENDIX D FREQUENTLY ASKED QUESTIONS FAQ It is the USB Serial Port COMx displayed in Windows Device Manger is the COMx port that sh...

Страница 133: ...OM to ODS301 I See Table 2 5 for further information on the 2 WIRE CURRENT connector Configure the module for operation with the type of the sensor measurement chain being used by the application In t...

Страница 134: ...se the 3 WIRE VOLTAGE connector with the following connections Sig gen High to ODS301 SIG and Sig gen Low COM GND to ODS301 V See Table 2 4 for further information on the 3 WIRE VOLTAGE connector And...

Страница 135: ...the Device status tab under Error status Current error provides information on any current problems Error memory provides information on any past problems that have not yet been acknowledged cleared u...

Страница 136: ...cess level is the default access level so the SpeedSys300 ODS301 module and SpeedSys300 software must be changed to the Admin access level before activating changing the configuration of a module NOTE...

Страница 137: ...ate In addition On the front panel of the SpeedSys300 ODS301 module the Error LED will show red On the Device status tab in the SpeedSys300 software the Error status will display an Analog output feed...

Страница 138: ...oltage level If a pull up resistor is not used the frequency speed output will only appear as a low level signal of the order of 100 mV Examples When interfacing to an external system the value of the...

Страница 139: ...that they continue to operate as expected see 1 1 2 SIL safety If there is any issue with these relay tests then the SpeedSys300 ODS301 module will detect this as a problem error and put the module i...

Страница 140: ...erence MAODS301 E SpeedSys300 ODS301 overspeed detection system Edition 4 May 2022 D 10 I am seeing a Relays PST failed message What should I check APPENDIX D FREQUENTLY ASKED QUESTIONS FAQ THIS PAGE...

Страница 141: ...cs tab If error persists the module must be returned to Meggitt SA 0000 0004 Factory settings error Bad CRC in one or more of the following parameter groups Device Configuration factory Diagnostics fa...

Страница 142: ...Relays partial stroke test PST failed Cyclic operability check of the relays failed One or more of the relays cannot be controlled as intended 0004 0000 Parameter value out of range Parameter values...

Страница 143: ...ODS301 Modbus registers related to main status parameters NOTE The Modbus registers in this data block are read only Table F 1 SpeedSys300 ODS301 Modbus registers main status parameters Address Name...

Страница 144: ...12 Slave supplies B13 Aout readback error B14 Rail supply out of range B15 24 V supply out of range B16 Master Vcc out of range B17 Relay PST error B18 Parameter value invalid B19 Master temperature o...

Страница 145: ...Output admin B7 Output factory B8 Admin password B9 Device config user default settings B10 Device config admin default settings B11 Measurement config default settings B12 Output admin default settin...

Страница 146: ...vel 0 Programming mode setting command Read write for each access level Code 0x33 Enter parameter programming mode Code 0x55 Restore admin default Code 0x66 Save current as default Code 0x77 Restore c...

Страница 147: ...or RPM s calculation 0510 curr_aout single R O Current analog output value mA 0512 curr_aout_fb single R O Current analog output feedback value mA 0514 max_rpm single R O Max velocity value registered...

Страница 148: ...V 0554 slave_v2_min single R O Min sensor voltage path 2 within last 50 ms V 0556 pp_test_stat uint16 R O Partial proof test input status 1 input active 0 inactive 0557 al_Rel1_active uint16 R O Acti...

Страница 149: ...tal output 0563 Reserved uint16 R O 0564 freq_2_curr single R O Current frequency measured on second pulse input auxiliary frequency measurement Hz 0566 freq_2_max single R O Max auxiliary frequency v...

Страница 150: ...Device config admin B3 2nd copy of Device config admin B4 1st copy of Device config factory B5 2nd copy of Device config factory B6 1st copy of Measurement config B7 2nd copy of Measurement config B8...

Страница 151: ...R O Slave ROM CRC Updated only in slave error response Value 0 means no slave errors 6518 slv_mloop_tm uint16 R O Slave main loop time s Updated only in slave error response Value 0 means no slave er...

Страница 152: ...put b 6532 calc_count_eval_f uint32 R O Count of evaluated frequency calculation 6534 calc_count_eval_a uint32 R O Count of evaluated acceleration calculation 6536 calc_count_est_f uint32 R O Count of...

Страница 153: ...O Min value of A D raw input 2 V monitor 1 7006 min_ad_3 uint16 R O Min value of A D raw input 3 A D feedback 1 7007 min_ad_4 uint16 R O Min value of A D raw input 4 I monitor 2 7008 min_ad_1 uint16 R...

Страница 154: ...MODBUS REGISTER DEFINITIONS 7023 measure_cmd uint16 R O Measurement command B0 B1 key selector 7024 da_out_1 uint16 R O Requested D A output value for output 1 7025 da_out_2 uint16 R O Requested D A...

Страница 155: ...note that in the parameter programming mode write access further depends on the access level setting User Admin or Factory which is controlled by access pass Modbus register 0100 Write access is only...

Страница 156: ...Level 0 2040 modbus_addr uint16 1 to 254 Level 0 Modbus address for RS 485 interface 2041 baud_rs485 uint16 0 to 5 Level 0 Coded baud rate for RS 485 interface 0 4800 1 9600 2 19200 3 38400 4 57600 5...

Страница 157: ...SpeedSys300 ODS301 Modbus registers module configuration factory Address Name Data type Range Access Description 3000 serial_number char16 Level 2 3008 schem_version char16 Level 2 3016 PCB_code char1...

Страница 158: ...h is 200 See also Modbus register 4005 acc_depth 4007 meas_mode uint16 Level 1 Info field only for reporting For information only 4008 rated_speed single 0 to 2100000 Level 1 Nominal speed Range defin...

Страница 159: ...min to bp_tout_max Level 1 Count out for bad pulses Min count of good pulses per one bad pulse Value 0 causes each bad pulse to immediately raise a diagnostic error Range defined in Diag config factor...

Страница 160: ...ror B18 Parameter value invalid B19 Master temperature over under range B20 USB interface active B21 n u initial safe always latching B22 UART watchdog B23 Slave runtime watchdog error B24 Slave start...

Страница 161: ...3 3 to 3 8 Level 2 Slave Vcc voltage maximum limit 5004 slv_vcc_min single 3 0 to 3 3 Level 2 Slave Vcc voltage minimum limit 5006 supl_sens_max single 12 to 30 Level 2 Max value of sensor supply vol...

Страница 162: ...of range B15 24 V supply out of range B16 Master Vcc out of range B17 Relay PST error B18 Parameter value invalid B19 Master temperature over under range B20 USB interface active B21 n u initial safe...

Страница 163: ...vel 2 Min value of sensor voltage limit setting 5042 temp_max single 40 to 120 Level 2 Max value of MCU temperature 5044 temp_min single 40 to 120 Level 2 Min value of MCU temperature 5046 bp_tout_max...

Страница 164: ...onfig uint16 Level 1 Relay 1 SIL status B0 Latching B1 n u B2 Overspeed B3 Underspeed B4 Acceleration max B5 Acceleration min B6 n u B7 Proof test B8 Non safety error 5501 rel2_config uint16 Level 1 R...

Страница 165: ...6 r1_del_sp_max uint32 0 to 1000000 Level 1 Relay 1 delay for overspeed alarm Unit 1 ms 5518 r2_del_sp_max uint32 0 to 1000000 Level 1 Relay 2 delay for overspeed alarm Unit 1 ms 5520 r3_del_sp_max ui...

Страница 166: ...vel 1 Digital out delay for min acceleration alarm Unit 1 ms 5556 r1_sp_max single v_min to v_max Level 1 Relay 1 overspeed alarm value Range defined in Output config factory 5558 r2_sp_max single v_m...

Страница 167: ...config factory 5594 do_acc_min single acc_min to acc_max Level 1 Digital out min acceleration alarm value Range defined in Output config factory 5596 r1_sp_max_hyst single v_min to v_max Level 1 Rela...

Страница 168: ...n alarm hysteresis Range defined in Output config factory 5630 r3_acc_min_hyst single acc_min to acc_max Level 1 Relay 3 min acceleration alarm hysteresis Range defined in Output config factory 5632 r...

Страница 169: ...0 ODS301 Modbus registers output configuration factory Address Name Data type Range Access Description 6000 cal_aout_4ma uint16 100 to 24000 Level 2 PWM value for 4 mA 6001 cal_aout_20ma uint16 100 to...