USER MANUAL
Document reference MAODS301/E
SpeedSys300 ODS301 overspeed detection system
Edition 4 - May 2022
3 - 12
Installation considerations
INSTALLATION OF A SPEEDSYS300 ODS301
provides an example of how to hardwire safety relay 1 of two SpeedSys300
ODS301 modules to obtain a 2oo2 voting logic structure.
Because a SpeedSys300 ODS301 module’s safety relays – relay 1 and relay 2 – are
double-pole single-throw (DPST) relays, there are several ways in which two modules can be
hardwired in parallel to obtain a 2oo2 voting logic structure.
illustrate the two different ways in which a 2oo2 voting logic structure
can be implemented using the safety relay 1 of two SpeedSys300 ODS301 modules.
Table 3-7:
2oo2 – using safety relay 1 of SpeedSys300 ODS301 modules (1)
SpeedSys300 ODS301
modules
2oo2 to customer
#1
#2
B17
↔
B17
↔
2oo2 connection to customer circuit
B18
↔
B18
↔
2oo2 connection to customer circuit
Table 3-8:
2oo2 – using safety relay 1 of SpeedSys300 ODS301 modules (2)
SpeedSys300 ODS301
modules
2oo2 to customer
#1
#2
B19
↔
B19
↔
2oo2 connection to customer circuit
B20
↔
B20
↔
2oo2 connection to customer circuit
Figure 3-5:
2oo2 – example using safety relay 1 of SpeedSys300 ODS301 modules