Document reference MAODS301/E
USER MANUAL
Edition 4 - May 2022
SpeedSys300 ODS301 overspeed detection system
5 - 7
Output tab
COMMISSIONING OF A SPEEDSYS300 ODS301
5.4 Output tab
The Output tab and its parameters are shown in
.
The output configuration enables the user to define the behaviour of the digital outputs (relays
and digital) as well as the analog output.
5.4.1 Output tab – Digital outputs
In general, each relay and the digital output can be configured individually. However, it is
important to note that for the safety relays (Relay 1 and Relay 2), certain configuration
parameters are restricted.
More specifically, for the safety relays, their configuration is fixed as normally energized /
de-energize to trip (that is, Inverted is always selected). And their operation is also always
connected to the module’s diagnostics so that a problem detected by the module will always
drive the safety relays to the safe state (that is, Diagnostics (safe state) is always selected).
Figure 5-3:
SpeedSys300 software – Output tab