6 Master/Slave Option
86
DOEF series
Matsusada Precision
2. Settings of the master unit
For master/slave operation, the number of connected slave units must be set to the master unit.
All other settings, such as operation mode, protection, and output, need to be done in the master unit.
[Setting the number of slave units]
Main Set 2 on the master unit, there is an item for setting the number of slave units.
In order to perform the master/slave operation, be sure to set the number of slave units connected first.
If the settings are not correctly done, the units will not operate properly.
Press the SET/SAVE switch to enter the setting state, use the downward "
▼
" movement switch to select
"MORE" and press the ENTER switch to open Main Set 2.
Use the downward "
▼
"movement switch to select "Slave Unit and set the number of slave units by turning
the DIAL."
Then press the SET/SAVE switch to save the setting.
When the number of slaves is changed, be sure to save the settings, set the POWER switch to OFF, and
then set the POWER switch to ON again to restart the unit.
Without rebooting the units, it may not operate properly.
[CAUTION]
The number of slave units can be set to 0 to 2, but when setting the number of slave units to 0, connect
the cable to the master unit only and do not connect it to the slave units.
Number of slave
units
Fig. Main Set 2 on master unit
LOC
DC
CV
AC
Ext Signal
Soft Start
Soft Stop
SYSTEM
Response
Sense
Slave Unit
1
Main Set
2
Matsusada
OFF
FAST
OFF
Vdc +10.003 V
Vrms 14.138 V
Irms 28.295 A
Idc +19.991A
<
MASTER
>
Содержание DOEF Series
Страница 1: ...Instruction Manual F RA 001 3R2 MODEL DOEF series B N 243 9 024 243 9 024 Rev 0 4 ...
Страница 15: ...2 External Appearance 7 DOEF series Matsusada Precision 2 3 Dimensions 2 3 1 400W Model ...
Страница 16: ...2 External Appearance 8 DOEF series Matsusada Precision 2 3 2 600W Model ...
Страница 17: ...2 External Appearance 9 DOEF series Matsusada Precision 2 3 3 1200W Model ...
Страница 121: ......
Страница 123: ......
Страница 124: ......