Setup and Maintenance Guide
57
Troubleshooting Guide
(continued)
Symptom
Likely Cause
Action(s) for Remedy
Time clock events do
not occur.
(a) Controller is in the
override screen.
(a) Press the
Home button to exit the override screen.
Sunrise or sunset
events do not occur at
the correct time.
(b) Timeclock is disabled. (b) Enable the timeclock. See the “Overrides” section in this
guide for more information.
(c) Time is not set.
(c) Set the time. See STEP 5 in this guide for more
information.
(d) Date is not set
correctly.
(d) Set the date. See STEP 5 in this guide for more
information.
(e) Location is not set
correctly.
(e) Set the location. See STEP 5 in this guide for more
information.
(f) Holiday schedule is in
effect.
(f) Check if there is a holiday on the date the event is not
occurring. See STEP 5 in this guide for more information.
Circuits are flashing
erratically.
(a) Duplicate panel
addresses.
(a) Check that all panel addresses are unique. The panel
address is listed on the Home screen. To change
addresses, see STEP 1 in this guide for more information.
(b) Duplicate control
station addresses.
(b) Check that the address of each control station is correct
and unique. See the
LCP128 Installation Guide
for more
information.
(c) Contact closure input
is controlling the
circuits.
(c) Confirm that the contact closure input into the system is
in a steady state. Verify this at every panel contact
closure input and at every OMX-AV.
(d) Control station link is
mis-wired.
(d) See the
LCP128 Installation Guide
for proper wiring. If a
T-tap was created to wire a control to the control station
link, it should be no longer than 8 ft. (2.44m).
(e) Timeclock events are
occurring.
(e) Check the timeclock events for the day or holiday that
coincide with the time of the erratic behavior. Holiday
schedules override the 7 daily schedules. See STEP 5 in
this guide for more information.
(f) Afterhours mode is
active.
(f) Afterhours mode may cause the lights to flash. See
STEP 5 in this guide for more information.