R
LCP128
TM
Setup and Maintenance Guide
15
Panel
Address 1
12
Circuits
System
Circuits
1-12
Panel
Address 2
24
Circuits
System
Circuits
13-36
Panel
Address 3
16
Circuits
System
Circuits
37-52
STEP 1
Panel Configuration
To program a
LCP128
panel, you need to:
•
Choose a language
for the controller LCD.
•
Set the panel configuration,
including:
•
Panel address
•
First circuit number in the panel
•
Number of circuits in the panel
Each circuit in the system is identified by a system circuit number. This number will be used to identify the
circuit for programming purposes. For example, if Panel 1 has 12 circuits, the first circuit in Panel 2 will be
circuit 13 on the
LCP128
controller. The figure below shows a sample system.
Note:
If your system has only one panel, you do not need to set the panel configuration. The panel address,
first system circuit number, and number of circuits are preprogrammed. However, for multi-panel systems,
you must set the panel configuration from the master panel (address 1) and then from each remote panel.
•
Configure the load setup,
including:
•
Module type setup
•
System size
•
Load type
•
High end trim
•
Low end trim
All system programming (covered in programming STEPS 2-7) is performed at
panel address 1
. In a multi-
panel system, panel address 1 becomes the master programming panel and all other panels are remote panels.
Remote panels have limited menu options and functionality.
Before proceeding with STEP 1, complete the Panel, Module Type, Load Type, and Control Station
Tables located at the back of this guide.
Master Panel
:
All system
programming
must take place
at this panel
First circuit in
this panel
First circuit in
this panel
First circuit in
this panel