R
18
LCP128
TM
Setup and Maintenance Guide
STEP 1 (continued)
Module Type Setup
Your
LCP128
system contains modules configured
with one or more outputs (circuits). The module
types are set by the model numbers of the panels
in the system. Complete the Module Type Table at
the back of this guide and then program the
module types for your system. The factory default
module type is X (4 Switches).
A.
From the
Main Menu
use and to
highlight
Panel Setup
and
press or (OK).
B.
Use and to
highlight
Load Setup
and press
or (OK).
C.
Use and to
highlight
Module Type Setup
and
press or (OK).
D.
The Module Type Setup screen lists all the circuits.
To program a module, use
and
to select the
first circuit number in the module and
and
to
set the module type.
Module type options include:
X:
Four-Circuit Switching (Relay) Module (XP)
S:
One-output (circuit) Dimming Module (1U)
D:
Two-output (circuit) Dimming Module (2U)
Q:
Four-output (circuit) Dimming Module (4U)
E:
Four-output (circuit) Electronic Low Voltage
Dimming Module (4E)
M:
Four-output (circuit) Motor Module (4M)
F:
Four-output (circuit) Quiet Fan Speed Module
(4FSQ)
Notes:
As you set each module type, the appropriate
circuit numbers are automatically assigned to the
module.
If you set the system size earlier in STEP 1, the
Module Type Setup screen lists only the circuits
used in your system.
E.
When all the module types are set press
or
(Done).
OK
OK
OK
OK
Load Setup
Module Type Setup
Chicago Setup
Low End Trim Setup
System Size
Back
OK
C.
Module Type Setup
001-004
- E:4 ELV
005-006
- D:2 dimmers
007-010
- X : 4 s w i t c h e s
Cancel
Done
D.
011-014
- Q:4 dimmers
Panel Setup
Load Setup
Panel Addressing
Emergency Setup
Afterhours Setup
Back
OK
B.