R
LCP128
TM
Setup and Maintenance Guide
19
STEP 1 (continued)
Load Type Setup
Complete the Load Type Table at the back of this
guide and then program the load types for your
system circuits. The factory default load type for
each circuit is Non-Dim.
Note:
If you are unsure of the load type for a
particular circuit, set the load type to Non-Dim
until the correct setting is determined.
A.
From the
Main Menu
use and to
highlight
Panel Setup
and
press or (OK).
B.
Use and to
highlight
Load Setup
and press
or (OK).
C.
Use and to
highlight
Load Type Setup
and
press or (OK).
D.
The Load Type Setup screen lists all the circuits.
For each circuit, use
and
to select the circuit
and
and
to select the load type.
Load type options depend on the module type
assigned to the circuit:
Switching:
Non-dim, DSI, 0-10V, DALI, PWM
Dimming:
Incandescent, MLV (Magnetic Low
Voltage), Tu-Wire (ballasts), Neon, ELV (Electronic
Low Voltage), Non-dim, DSI, 0-10V, DALI, PWM
Motors:
Motor
Fans:
Fan
N
No
otte
e:: Switching or dimming modules controlling
DSI, 0-10V, DALI, or PWM load types require
TVM(s).
E.
When all the load types are set press
or
(Done).
Load Type setup is now complete and all
settings are saved in the event of a power
failure.
OK
OK
OK
OK
Panel Setup
Load Setup
Panel Addressing
Emergency Setup
Afterhours Setup
Back
OK
B.
Load Setup
Load Type Setup
High End Trim Setup
Low End Trim Setup
Chicago Setup
Back
OK
C.
Load Type Setup
001
Dim
- Incandescent
002
Dim
- ELV
003
Relay
- N o n - D i m
Cancel
Done
D.
004
Dim
- Tu-Wire
Caution!
Failure to correctly assign load types
may damage loads, especially certain
electronic transformers, electronic ballasts,
and motors. Verify with the transformer or
ballast manufacturer that the product can be
dimmed with phase control dimming before
setting to any load type other than Non-Dim.