R
LCP128
TM
Setup and Maintenance Guide
29
STEP 4
Control Stations
Control stations are connected to the
LCP128
panel via the digital control link. Control stations can be
wallstations (with various numbers of buttons), key switches (NTOMX-KS), contact closure input and output
devices (OMX-AV), contact closure output devices (OMX-CCO-8), or OMX-RS232 interfaces. Each control
station must be assigned a unique address. Addressing may be found in either the
LCP128 Installation Guide
or installation guides for the individual devices. To set the address, refer to the instructions for each device.
Every wallstation button, key switch, or contact closure input can be assigned one of the following functions:
•
Scene
- A scene consists of a specified light level and fade time. Each time the button, key switch, or contact
closure input is activated, the assigned circuits go to the programmed scene. A scene can also be used to
control contact closure outputs.
•
Custom Scene
- A custom scene is a scene assigned to and programmed for a specific button press, key
switch turn, or contact closure input. A custom scene may be recalled only by that single action to which it is
assigned.
•
Lower Circuits
- Assigned dimming circuits are progressively lowered as long as input is received from the
control station (for example, the button is held down, key is turned, contact closure is maintained). Circuits stay
at this setting until another event or control station input occurs.
•
Raise Circuits
- Assigned dimming circuits are progressively raised as long as input is received from the control
station (for example, the button is held down, key is turned, contact closure is maintained). Circuits stay at this
setting until another event or control station input occurs.
•
Toggle
- Each time the button, key switch, or contact closure input is activated, the assigned circuits toggle
between on and off. If the assigned circuits are in a mixed state (some on and some off), the circuits turn on.
•
Delay To Off
- Each time the button, key switch, or contact closure input is activated, the assigned circuit(s) turn
off after the preset amount of time (1 - 90 minutes).
•
Enable Time Clock
- Enable the function of the time clock.
•
Disable Time Clock
- Disable the function of the time clock.
Before proceeding with STEP 4, complete the Control Station Table at the back of this guide. Record
what each input (button, key switch, or contact closure) on each control station should do.
Note:
In STEP 4, you will configure contact closure inputs wired to a Lutron OMX-AV control station.
Contact closure inputs wired directly to a panel are configured later in STEP 6.