Setup and Maintenance Guide
STEP 4 (continued)
Configure Contact Closure
Inputs on OMX-AV
Lutron’s OMX-AV control station can be
programmed to initiate actions for up to five contact
closure inputs.
Note:
For contact closure inputs wired directly to
the LCP128 panel, refer to STEP 6.
A.
From the
Main Menu
use and to
highlight
Control Station Setup
and
press or (OK).
B.
Use
and
to highlight the address of the
OMX-AV
you would like to configure and press
or (Next).
C.
Use
and
to set the control
Type
to
OMX-AV
and
press or (Next)
.
D.
Each OMX-AV provides 5 inputs. Use
and
to
highlight the
Contact Closure Input (CCI)
to
program and press
or
(Next). Or select
No CCI’s
if only the contact closure outputs (CCOs)
are being used.
E.
Use
and
to select whether you want define an
action for when the contact opens or when it
closes and press
or
(Next).
Note:
If there should be an action on both, first
set up the
Open Action
, then follow this
procedure again but choose
Closure Action
.
F.
Use
and
to select the type of
Action
for this
CCI:
Lower Circuits
,
Raise Circuits
,
Scene
,
Custom Scene
,
Enable Time Clock, Disable
Time Clock, Delay to Off
,
Toggle,
and
No Action
and press
or
(Next). Refer to the beginning of
STEP 4 for an explanation of the various action
types.
G.
Program the
Lower Circuits
,
Raise Circuits
,
Scene
,
Custom Scene
,
Delay to Off
, or
Toggle
action using the same screen methods used to
configure a wallstation button. Refer to “Configure
the Wallstations” earlier in STEP 4.
OK
OK
OK
OK
OK
OK
Address 03 Setup
Type:
OMX-AV
Previous
Next
Address 03 CCI 2 Setup
Open Action
Closure Action
Previous
Next
Main Menu
Overrides
Time Clock Setup
Control Station Setup
etup
Panel CCI Setup
Back
OK
Control Station Setup
Address 01
Address 02
Address 03
Address 04
Previous
Next
A.
B.
C.
E.
Address 03 OMX-AV
No CCI’s
CCI 01
CCI 02
CCI 03
Previous
Next
D.