R
50
LCP128
TM
Setup and Maintenance Guide
Overrides
(continued)
Override the Circuits by
Setting Circuit Levels
A.
From the
Main Menu
use and to
highlight
Overrides
and
press or (OK).
Note:
From a remote panel, choose
Set Circuit
Levels
from the
Main Menu
.
B.
Use and to
choose
Set Circuit Levels
and
press or (OK)
C.
The circuits are listed with their current settings
displayed. Use
and
to select a circuit and
and
to change the setting for that circuit. To
change all circuits, select A
Allll C
Ciirrc
cu
uiitts
s and use
and
to change the setting.
Note:
The
All Circuits
function enables you to
adjust the percentage for all dimming circuits or
to turn all circuits off and on.
Circuit settings depend on the circuit type:
Switching:
ON, OFF, Flash
Dimming:
OFF, 1 - 100%, Flash
Motors:
Open, Close, Stop, Jog Up, Jog Down
Fans:
Low, Medium, Medium-High, High
Note:
The
Flash
setting cycles a circuit between
On and Off once every few seconds - useful for
locating a circuit in the space.
Changes take effect immediately. As long as the
Set Circuit Levels screen is displayed, the circuits
will remain at the set state. The settings override all
other inputs (time clock events, button presses,
contact closure inputs, etc.).
The override Set Circuit Levels screen will not time-
out to the Home screen or screen saver.
D. To exit the Set Circuit Levels screen and keep
the changed settings,
press or (Done).
The
circuits will remain at the override setting until they
are changed by a control station input or time clock
event.
To exit the Set Circuit Levels screen and return
the circuits to what they were before setting
overrides,
press (Cancel).
*
OK
OK
OK
Set Circuit Levels
All Circuits
- - - -
001
Dim
- FLASH
002
Dim
- 100%
003
Relay
- O N
Cancel
Done
Main Menu
Overrides
Time Clock Setup
Control Station Setup
Panel CCI Setup
Back
OK
Overrides
Set Circuit Levels
Timeclock Override
Select Scene
Control Stations Override
Back
OK
A.
B.
C.