SmartDGA Hardware Manual
Pre-Installation Verification
•
19
VA-2 (Dual Valve)
Description
Thread Type
Clearance
(Distance)
Use this kit when there is a
bottom drain valve and a
return valve available on
the transformer. This valve
kit is compatible with ball,
gate, plug, globe, and
butterfly valves.
Mount (Bottom) Valve
Confirm that the thread type
for the valve is female 1” NPT.
If it is not a 1” NPT thread
type, you will need an NPT
reducer. Verify that you have a
reducer on hand.
To Left of the Valve > 18” (45.7 cm)
To Right of the
Valve > 18” (45.7 cm)
Bottom to Ground > 12” (30 cm)
Top to Obstruction > 17” (43.2 cm)
Return (Top) Valve
Confirm that return valve
accepts 3/8” tubing. If it is not,
you may need an NPT reducer
and adapter to decrease the
present transformer return
valve size to accept 3/8”
tubing. You can also purchase
a Swagelok adapter (PN SS-
600-1-16) that will thread into
the female 1” reducer and
accept 3/8” tubing.
Vertical distance
from the drain valve
to the return valve
3’ to 20’
(0.91 m to 6.1 m)
Piping distance from
the drain valve to
the return valve
< 32.8’ (10.0 m)
Number of right
angles to the return
valve for piping
< 5 turns
VA-0 (Inline or Off-Transformer)
Description
Clearance
(Distance)
Use this kit any time the SmartDGA
instrument cannot be mounted directly on
the transformer valve or when connecting
the SmartDGA Gauge instrument to a LTC
tank.
Mounting Plate
The support for the mounting plate must
be capable of holding at least 50 pounds
(22 kg) and mounted near the transformer
or LTC filter. The typical support will either
be the transformer wall or a Unistrut post
supported by concrete.
The location chosen must be appropriate
for the support and allow for oil lines to
and from the transformer or LTC filter. If
installing in a cold climate where the oil
will reach a temperature of
-10 °C or less in the lines, the lines must be
heated, otherwise the oil will be too
viscous to be pumped by the SmartDGA
instrument.
Left of the mounting plate > 18” (45.7 cm)
Right of the mounting plate > 18” (45.7 cm)
Mounting plate to the ground > 12” (30 cm)
Mounting plate to the top obstruction > 17” (43.2 cm)
Vertical distance from the
instrument to the oil ports
3’ to 20’
(0.91 m – 6.1 m)
Piping distance from the instrument
to the outlet/return port
< 32.8’
(10.0 m)
Number of right angles to the
outlet/return port for piping < 5 turns
Piping distance from the instrument
to the inlet/feed port
< 32.8’
(10.0 m)
Number of right angles to the
inlet/feed port for piping < 5 turns
Содержание SmartDGA
Страница 1: ...HARDWARE MANUAL SmartDGA...
Страница 99: ...SmartDGA Hardware Manual Diagrams Drawings 99 9 5 SmartDGA NEMA 4 Enclosure...
Страница 100: ...SmartDGA Hardware Manual Diagrams Drawings 100 9 6 Inline Mounting Plate...
Страница 102: ...SmartDGA Hardware Manual Diagrams Drawings 102 9 8 Assy Wall Mount SmartDGA EZHubTM...
Страница 103: ...SmartDGA Hardware Manual Diagrams Drawings 103...
Страница 104: ...SmartDGA Hardware Manual Diagrams Drawings 104 9 9 Assy Panel Mount SmartDGA EZHubTM...
Страница 105: ...SmartDGA Hardware Manual Diagrams Drawings 105...
Страница 106: ...SmartDGA Hardware Manual Diagrams Drawings 106 9 10 Assy Wall Mount LumaSMART iCoreTM...
Страница 107: ...SmartDGA Hardware Manual Diagrams Drawings 107...
Страница 108: ...SmartDGA Hardware Manual Diagrams Drawings 108 9 11 Assy Panel Mount LumaSMART iCoreTM...
Страница 109: ...SmartDGA Hardware Manual Diagrams Drawings 109...
Страница 110: ...SmartDGA Hardware Manual Diagrams Drawings 110 9 12 SmartDGA Instrument Sun Shade...
Страница 111: ...SmartDGA Hardware Manual Diagrams Drawings 111...