Chapter 2 Hardware Description
AC 60 System Environmental Specifications
appear on surfaces. The temperature and relative humidity must be kept
within the specified tolerance limits as shown in Table 2-2.
Facility Power Source Requirements
Three types of built-in Power Supply components are available for the AC 60
system:
•
110 V ac Power Supply
•
220 V ac Power Supply
•
-48 V dc Power Supply
WARNING:
!
Be sure that you have adequate wiring capacity and fuse panel/circuit
breaker capacity to accommodate all AC 60 systems and other
equipment you plan to install. Insufficient capacity will cause fuses to fail
or circuit breakers to trip.
Table 1 provides the facility power source requirements for the operation of
one AC 60 system. Use these specifications for one chassis to calculate how
much electrical supply capacity you would need for multiple systems.
Table 2-2. Environmental Specifications for the AC 60 System
Specification
Range of Values
Operating temperature:
32° to 122° F
0° to 50° C
Storage temperature:
-40° to +158° F
-40° to +70° C
Operating relative humidity:
40 to 60%, optimum;
Up to 95°%, noncondensing
Table 1. AC 60 Power Source Requirements
Specification
Description
AC power source for the 110 V ac Power Supply:
Voltage range:
90 to 130 V ac at 50 to 60 Hz
Maximum current:
5 A
Maximum power:
300 W
AC power source for the 220 V ac Power Supply:
Voltage range:
180 to 250 V ac at 50 to 60 Hz
Maximum current:
2.5 A
Maximum power:
300 W
DC power source for the -48 V dc Power Supply
Voltage range:
-48 V dc