Lucent Technologies Lineage
®
2000 400A, 60Hz Ferroresonant Rectifier J85503C-3
5 - 2 Installation
Issue 10 July 2000
Guidelines
Location of the J85503C-3 rectifier and associated equipment must
conform to the specific plans of each plant installation. Physical,
thermal, and electrical characteristics are listed in Section 2. Consider
these characteristics when planning any installation that includes this
rectifier.
Floor Mounting
The J85503C-3 is a floor-mounted rectifier with four anchoring holes
located in the base. The rectifier must be anchored to all types of
flooring including masonry, wood, and raised floors. Since these
rectifiers are too heavy for using the rectifier as a “hole locating
template,” a paper template is provided to locate, drill, and set floor
anchors before placing the rectifier. Figure 5-1 is a picture of this
template showing the anchor holes, measurements, and instructions for
drilling anchor holes for installation in earthquake zones 3 or 4. (Anchor
bolts for Zones 0, 1, and 2 are self-drilling.) See Table 3-B for anchor
bolt ordering information. The anchor bolts are self-drilling. Figure 5-2
shows these floor anchors.
Rectifier cabinets must be aligned and shimmed to satisfy plumbing
requirements, and the floor anchors secured against the shims.
Removing the rectifier bottom-front kickplate provides the installer with
about six inches of vertical working space in the base of the cabinet for
access to the anchors.
Figure 5-1: Floor Mounting Detail
27.14
(68.93cm)
.60
(1.52 cm)
1.00 in. (2.54 cm) diameter
clearance holes for anchors
.60
(1.52 cm)
16.89
(42.90 cm)
1.41
(3.58 cm)
25.95
(65.89 cm)
21.50
(54.61 cm)
2.22
(5.64 cm)
14.88
(37.80 cm)
9.12
(23.16 cm)
3.57
(9.07 cm)