2 - 14 Product Description
Issue 10 July 2000
Alarm and
Control Flow
The J85503C-3 400-ampere rectifier is typically installed in a battery
plant that is monitored and controlled by a Lucent Technologies
Lineage
®
2000 controller. The rectifier generates various monitoring
and alarm signals and, in this type of installation, sends them to the
controller for processing and subsequent action. The action may be local
or remote alarm indications or control signals fed back to the rectifier.
Refer to the various controller product manuals for a description of
rectifier signal processing and resultant action.
Figure 2-3 shows the typical signal flow between a rectifier and a
Galaxy controller. The control signals and alarms enter and leave the
rectifier via the interface board, CM4. When used with a non-Lucent
Technologies controller or if additional monitoring is desired, interface
to TB1, TB2, and TB3 of the 330B interface board. The plant
controllers also use replaceable circuit modules.
Refer to H285-226 to order cable assemblies for other Galaxy
configurations, the ECS-6U, ECS-12U, the MCS, and the CCS
controllers.
Figure 2-3: Signal Flow Rectifier/Galaxy Controller
Galaxy
Controller
Plant Control Cable Assembly
H285226 G-60
DC Output Circuit Breaker Status (CB)
RFA Test
Load Share Fail (LSF)
AC Fail (ACF)
Low Current Alm (LCA)
Power Switch Status (MAN)
Rectifier Shutdown (TR)
Rectifier Current Capacity (TP)
Rectifier Failure Alarm (RFA)
Rectifier Restart (RS)
Rectifier Current Drain (VI)
Rectifier Efficiency Algorithm (TRH)
Phase Failure Alarm (PHA)
Rectifier Regulation (R+, R–)
CM4
Interface
Board
330C
Rectifier