Lucent Technologies Lineage
®
2000 400A, 60Hz Ferroresonant Rectifier J85503C-3
2 - 8 Product Description
Issue 10 July 2000
Front Panel
Controls and
Indicators
Figure 2-1 shows the control panel on front of the J85503C-3,
400-ampere rectifier. The following list describes the controls and
indicators on the control panel. Bold letters indicate labels that appear
on the control panel or inside the rectifier.
Note: “Equal Adj” and “EQ” LEDs on the control panel may be labeled
“Boost” and “BST,” respectively, for international customers.
Output Meter
The digital Output meter displays the following:
•
The rectifier output current when the meter switch is in the Amps
position
•
The rectifier output voltage when the meter switch is in the Rect V
position
•
The battery voltage when the meter switch is in the Plt V position
Rect V
The user may select whether the default position of the meter switch is
rectifier current or battery voltage. Otherwise, moving the switch
momentarily to the Rect V position displays the rectifier voltage. The
user may also select the option of having the meter active when the
rectifier is manually turned off.
Power Switch
The Power switch turns the rectifier On, Off, or puts it in the Auto
mode for remote control via a signal to the interface board. A green LED
lights when the rectifier is on.
Figure 2-1: J85503C-3 Control Panel
Output
Power
On
Auto
Off
Plant
PHA
FA
RFA
ACF
LCA
LSF
Alarm
Rect
FL
NL
Equal Adj
Rect V
Rect
Test
FLT
EQ
Amps
Plt V
Float
Adj