Lucent Technologies Lineage
®
2000 400A, 60Hz Ferroresonant Rectifier J85503C-3
Issue 10 July 2000
Engineering and Ordering 3 - 9
19. If local codes permit, you may connect an overhead raceway to the
rectifier with flex steel conduit. Flex steel conduit kit (846860682)
comes complete with 17 inches of 1-1/4 inch diameter flex steel
conduit, two KS20785 L-39 connectors, and two KS20785 L-114
insulating bushings.
20. Use the cable ties provided with the plant to secure the plant
control cable to the top frame vertical post. The control cable
should pass through the spiral wrap to the door where it is
mounted with push-in tie wraps. You must secure a tie wrap to the
control cable just above the top lid grommet so that the control
cable cannot enter the rectifier cabinet. Do not, under any
circumstance, toll the control cable up inside the rectifier. Roll up
any extra length of control cable and tie it up at the controller.
21. The J85503C-3 rectifier is capable of forced load share with other
J85503C-3 rectifiers. It will not load share with a J85503C-1
rectifier.
22. For international applications, place the two labels on the face
plate. The definition for boost in the international market is the
same as equalize for the domestic market.
23. Order spare circuit packs for the J85503C-3 rectifier per table 3-D.
Table 3-D: Circuit Packs in the J85503C-3 Rectifier
Circuit
Module
Apparatus Code
Comcode
Description
CM1
329A
106295280 Fuse Board
CM2
208F1
107199184 Control Board
CM3
323D
106938137 Digital Meter Board
CM4
330C
107199192 Interface Board
CM5/CM6
ED83156-30 G-3 601326408 Snubber Board
CM7 (List 1)
425C
107134454 Transformer Board
CM7 (List 2)
425D
107134462 Transformer Board
CM7 (List 3)
425F
107134488 Transformer Board
CM7 (List 4)
425E
107134470 Transformer Board