Lucent Technologies Lineage
®
2000 400A, 60Hz Ferroresonant Rectifier J85503C-3
5 - 20 Installation
Issue 10 July 2000
323D Digital Meter
Board (CM3)
S3.1 through S3.4 tell the rectifier's ammeters the rectifier's current
capacity.
S3.5 through S3.6 configure the NL/FL switch on the front of the
rectifier for either 24 or 48 volts.
329A Fuse Board
(CM1)
S1.1 through S1.4 are not field adjustable.
330C Interface
Board (CM4)
S2.1 enables the front panel equalize switch on the rectifier.
S2.2 keeps the front panel display on or off when the control switch is
in the off position. When S2.2 is on, the front panel display is always on.
When S2.2 is off, the front panel display is off when the rectifier is
turned off either via the front panel or via the controller.
S2.3-S2.6 configure the rectifier for operation with a 24- or 48-volt
plant.
Converting
AC Voltage
The main list number of the J85503C-3 rectifier (Lists 1, 2, 3, or 4)
determines the ac input voltage of the unit. (See Table 3-A.) List 1 has
208-volt ac input and uses the 425C transformer board. List 2 has
240-volt ac input and uses the 425D transformer board. List 3 has
480-volt ac input and uses the 425F transformer board. List 4 has
416-volt ac input and uses the 425E transformer board. Each list number
requires different connections to windings of main transformers T1 and
T2.
Underwriters Laboratory, Inc. (UL) requires the proper circuit module,
wiring configuration, input, and product identifying labels for any unit.
Therefore, only Lucent Technologies installation personnel are
permitted to implement ac input conversions.