Lucent Technologies Lineage
®
2000 400A, 60Hz Ferroresonant Rectifier J85503C-3
Issue 10 July 2000
Engineering and Ordering 3 - 7
4. The following items are shipped with each rectifier:
• mounting template
• top mounting plates
• ac input connectors
• frame ground connector
5. The central office ground connector, the mounting anchor bolts
(kit), and the dc output connectors are not provided with the
rectifier. Order these items from Table 3-B.
6. Use approved tooling for crimping connectors.
7. The standard output circuit breaker provided with Lists 1, 2, 3, and
4 is a 450 ampere breaker and meets Bellcore standard
TR-EOP-000151 issue 1 for output protection. The optional output
circuit breaker (List 6) provides a 500 ampere circuit breaker and
meets GTE standard 8336 issue 1 for output protection.
8. When installing J85503C-3 rectifiers in a plant with other Lucent
Technologies Lineage
®
2000 rectifiers, cut lead 13 of the interface
cable of all the rectifiers not equipped with an equalize feature to
prevent the J85503C-3 rectifier from being placed permanently in
an equalize mode of operation.
Table 3-B: Hardware
Equipment
Requirement Qty Description
Comcode
Anchor Bolts (Kit) Zone 3 or 4
1
H569-407
G-6
847320835
Anchor Bolts (Kit) Zone 0, 1, or 2
1
H569-407
G-1
847135654
DC Output
Connectors
4/0 AWG
Class B
4
WP91412
L-59
405348251
DC Output
Connectors
4/0 AWG Flex
4
WP91412
L-27
405347923
DC Output
Connectors
350KCMIL
Class B
4
WP91412
L-61
405348277
DC Output
Connectors
350 KCMIL
AWG Flex
4
WP91412
L-86
406021915
CO Ground
Connectors
Class B
1
WP91412
L-54
405348202
CO Ground
Connectors
Flex
1
WP91412
L-8
405347683