![LSIS G100 Скачать руководство пользователя страница 84](http://html.mh-extra.com/html/lsis/g100/g100_operation-manual_1944296084.webp)
Code and
Features
Description
In.65
–69 Px
Define
Choose the P1-P5 terminals to setup as multi-step inputs, and then set
the relevant codes (In.65
–69) to 7 (Speed-L), 8 (Speed-M), or 9
(Speed-H).
Provided that terminals P3, P4 and P5 have been set to Speed-L,
Speed-M and Speed-H respectively, the following multi-step operation
will be available.
[An example of a multi-step operation]
Speed
Fx/Rx
P5
P4
P3
0
-
-
-
1
-
-
2
-
-
3
-
4
-
-
5
-
6
-
7
[An example of a multi-step speed]
In.89 InCheck
Time
Set the time for the inverter to check for other terminal block inputs.
After adjusting In.89 to 100 ms and an input signal is received at P5,
the inverter will search for inputs at other terminals for 100 ms, before
proceeding to accelerate or decelerate based on P5’s configuration.
Содержание G100
Страница 14: ......
Страница 16: ...5 5 7 5 kW 3 Phase ...
Страница 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Страница 48: ......
Страница 68: ......
Страница 81: ......
Страница 100: ......
Страница 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Страница 118: ......
Страница 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Страница 140: ... PID control block diagram ...
Страница 165: ...Code and Features Description Code Description continuous rating ...
Страница 170: ......
Страница 186: ... Displayed as on the Keypad ...
Страница 200: ...provided signal output at 150 36 sec ...
Страница 216: ...Code and Features Description delay time delay time ...
Страница 219: ......
Страница 237: ......
Страница 253: ......
Страница 295: ......
Страница 314: ......
Страница 330: ...11 10 Remote Keypad Option It is comprised of a remote keypad and cables 1 m 2 m 3 m and 5 m Units mm ...
Страница 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...