2.4 Test Run
After the post-installation checklist has been completed, follow the instructions below
to test the inverter.
1
Turn on the power supply to the inverter. Ensure that the keypad display light is
on.
2
Select the command source.
3
Set a frequency reference, and then check the following:
•
If V1 is selected as the frequency reference source, does the reference change
according to the input voltage?
•
If I2 is selected as the frequency reference source, does the reference change
according to the input current?
4
Set the acceleration and deceleration time.
5
Start the motor and check the following:
•
Ensure that the motor rotates in the correct direction. If the motor is rotating in
the reverse direction, refer to the details below.
•
Ensure that the motor accelerates and decelerates according to the set times,
and that the motor speed reaches the frequency reference.
Note
If the forward command (Fx) is on, the motor should rotate counterclockWise when
viewed from the load side of the motor. If the motor rotates in the reverse direction,
switch the cables at the U and V terminals.
Remarque
Si la commande avant (Fx) est activée, le moteur doit tourner dans le sens anti-
horaire si on le regarde côté charge du moteur. Si le moteur tourne dans le sens
inverse, inverser les câbles aux bornes U et V.
Verifying the Motor Rotation
1
On the keypad, set the drv (Frequency reference source) code in the Operation group
to 0 (Keypad).
Содержание G100
Страница 14: ......
Страница 16: ...5 5 7 5 kW 3 Phase ...
Страница 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Страница 48: ......
Страница 68: ......
Страница 81: ......
Страница 100: ......
Страница 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Страница 118: ......
Страница 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Страница 140: ... PID control block diagram ...
Страница 165: ...Code and Features Description Code Description continuous rating ...
Страница 170: ......
Страница 186: ... Displayed as on the Keypad ...
Страница 200: ...provided signal output at 150 36 sec ...
Страница 216: ...Code and Features Description delay time delay time ...
Страница 219: ......
Страница 237: ......
Страница 253: ......
Страница 295: ......
Страница 314: ......
Страница 330: ...11 10 Remote Keypad Option It is comprised of a remote keypad and cables 1 m 2 m 3 m and 5 m Units mm ...
Страница 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...