Pr.50 Stall
Prevent
Stall prevention can be configured for acceleration, deceleration, or
while operating a motor at constant speed. When the top LCD
segment is on, the corresponding bit is set. When the bottom LCD
segment is on, the corresponding bit is off.
Items
Bit On Status
Bit Off Status
Keypad
Configuration
Function
bit4
bit3
bit2
bit1
Stall protection during
acceleration
Stall protection while operating
at a constant speed
Stall protection during
deceleration
Flux braking during
deceleration
Configuration
Function
0001
Stall
protectiond
uring
acceleratio
n
If inverter output current exceeds the preset
stall level (Pr. 52, 54, 56, 58) during
acceleration, the motor stops accelerating
and starts decelerating. If current level stays
above the stall level, the motor decelerates
to the start frequency (dr.19). If the current
level causes deceleration below the preset
level while operating the stall protection
function, the motor resumes acceleration.
0010
Stall
protection
while
operating
at constant
speed
Similar to stall protection function during
acceleration, the output frequency
automatically decelerates when the current
level exceeds the preset stall level while
operating at constant speed. When the load
current decelerates below the preset level, it
resumes acceleration. During acceleration,
the operation will follow the stall protection
settings for acceleration.
0100
Stall
protection
during
deceleratio
n
The inverter decelerates and keeps the DC
link voltage below a certain level to prevent
an over voltage fault trip during deceleration.
As a result, deceleration times can be longer
than the set time depending on the load.
Содержание G100
Страница 14: ......
Страница 16: ...5 5 7 5 kW 3 Phase ...
Страница 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Страница 48: ......
Страница 68: ......
Страница 81: ......
Страница 100: ......
Страница 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Страница 118: ......
Страница 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Страница 140: ... PID control block diagram ...
Страница 165: ...Code and Features Description Code Description continuous rating ...
Страница 170: ......
Страница 186: ... Displayed as on the Keypad ...
Страница 200: ...provided signal output at 150 36 sec ...
Страница 216: ...Code and Features Description delay time delay time ...
Страница 219: ......
Страница 237: ......
Страница 253: ......
Страница 295: ......
Страница 314: ......
Страница 330: ...11 10 Remote Keypad Option It is comprised of a remote keypad and cables 1 m 2 m 3 m and 5 m Units mm ...
Страница 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...