4.13 Motor Output Voltage Adjustment
Output voltage settings are required when a motor’s rated voltage differs from the
input voltage to the inverter. Set the voltage value to configure
the motor’s rated
operating voltage. The set voltage becomes the output voltage of the inverter’s base
frequency. If bA.15 (motor rated voltage) is set to 0, the inverter corrects the output
voltage based on the input voltage in the stopped condition. If the frequency is higher
than the base frequency, when the input voltage is lower than the parameter setting,
the input voltage will be the inverter output voltage.
Group
Code
Name
Setting
Setting Range
Unit
bA
15
Motor rated voltage 0
0, 100-480
V
4.14 Start Mode Setting
Select the start mode to use when the operation command is input with the motor in
the stopped condition.
4.14.1 Accelerating Start
Acceleration start is a general acceleration mode. If there are no extra settings applied,
the motor accelerates directly to the frequency reference when the command is input.
Group
Code
Name
Setting
Setting Range
Unit
Ad
07
Start Mode
0
Acc
0
–1
-
Содержание G100
Страница 14: ......
Страница 16: ...5 5 7 5 kW 3 Phase ...
Страница 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Страница 48: ......
Страница 68: ......
Страница 81: ......
Страница 100: ......
Страница 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Страница 118: ......
Страница 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Страница 140: ... PID control block diagram ...
Страница 165: ...Code and Features Description Code Description continuous rating ...
Страница 170: ......
Страница 186: ... Displayed as on the Keypad ...
Страница 200: ...provided signal output at 150 36 sec ...
Страница 216: ...Code and Features Description delay time delay time ...
Страница 219: ......
Страница 237: ......
Страница 253: ......
Страница 295: ......
Страница 314: ......
Страница 330: ...11 10 Remote Keypad Option It is comprised of a remote keypad and cables 1 m 2 m 3 m and 5 m Units mm ...
Страница 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...