Code and
Features
Description
Pr.79 FAN
Trip Mode
Set the cooling fan fault mode.
Configuration
Function
0
Trip
The inverter output is blocked and the fan trip
is displayed when a cooling fan error is
detected.
1
Warning
When OU.33 (Relay 2) and OU.31 (Relay 1)
are set to 8 (FAN Warning), the fan error signal
is output and the operation continues.
OU.31 Relay 1,
OU.33 Relay 2
When the code value is set to 8 (FAN Warning), the fan error signal
is output and operation continues. However, when the inverter inside
temperature rises above a certain level, output is blocked due to
activation of overheat protection.
6.3.2 Lifetime Diagnosis of Components
Lifetime Diagnosis for Fans
Enter the Pr-87 (Fan exchange warning level) code (%). After the selected usage (%)
is reached (out of 50,000 hours), the fan exchange warning message will appear in
the multi-functional output or keypad.
The total fan usage level (%) appears at Pr-86. When exchanging fans, you may
initialize the accumulated value to 0 by setting the Pr-88 (Initializing accumulated time
for cooling fans) to 1.
Group Cod
e
Name
Setting
Setting Range
Unit
Pr
86
Accumulated percent of
fan usage
0.0
0.0
–6553.5
%
87
Fan exchange warning
Level
90.0
0.0
–100.0
%
OU
31
Multi-function relay 1
item
37 FAN Exchange
-
-
33
Multi-function relay 2
item
6.3.3 Low Voltage Fault Trip
When inverter input power is lost and the internal DC link voltage drops below a
certain voltage level, the inverter stops output and a low voltage trip occurs.
Содержание G100
Страница 14: ......
Страница 16: ...5 5 7 5 kW 3 Phase ...
Страница 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Страница 48: ......
Страница 68: ......
Страница 81: ......
Страница 100: ......
Страница 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Страница 118: ......
Страница 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Страница 140: ... PID control block diagram ...
Страница 165: ...Code and Features Description Code Description continuous rating ...
Страница 170: ......
Страница 186: ... Displayed as on the Keypad ...
Страница 200: ...provided signal output at 150 36 sec ...
Страница 216: ...Code and Features Description delay time delay time ...
Страница 219: ......
Страница 237: ......
Страница 253: ......
Страница 295: ......
Страница 314: ......
Страница 330: ...11 10 Remote Keypad Option It is comprised of a remote keypad and cables 1 m 2 m 3 m and 5 m Units mm ...
Страница 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...