Code and
Features
Description
5
Output
Power
Monitors output wattage. 200% of rated output is
the maximum display voltage (10 V).
6
Idse
Outputs the maximum voltage at 200% of no load
current. Outputs 0 V during V/F operation or slip
compensation operation since it is an output of the
magnitude of the current on the magnetic flux
portion.
7
Iqse
Outputs the maximum voltage at 250% of rated
torque current.
8
Target
Freq
Outputs set frequency as a standard. Outputs 10 V
at the maximum frequency (dr.20).
9
Ramp
Freq
Outputs frequency calculated with Acc/Dec function
as a standard. May vary with actual output
frequency. Outputs 10 V.
12
PID Ref
Value
Outputs command value of a PID controller as a
standard. Outputs approximately 6.6 V at 100%.
13
PID Fdk
Value
Outputs feedback volume of a PID controller as a
standard. Outputs approximately 6.6 V at 100%.
14
PID
Output
Outputs output value of a PID controller as a
standard. Outputs approximately 10 V at 100%.
15 Constant Outputs OU.05 (AO1 Const%) value as a standard.
OU.02 AO1 Gain,
OU.03 AO1 Bias
Adjusts output value and offset. If frequency is selected as an output
item, it will operate as shown below.
𝐴𝑂1 =
𝐹𝑟𝑒𝑞𝑢𝑒𝑛𝑐𝑦
𝑀𝑎𝑥𝐹𝑟𝑒𝑞
× 𝐴𝑂1 𝐺𝑎𝑖𝑛 + 𝐴𝑂1 𝐵𝑖𝑎𝑠
The graph below illustrates the analog voltage output (AO1) changes
depend on OU.02 (AO1 Gain) and OU.3 (AO1 Bias) values. Y-axis is
analog output voltage (0
–10 V), and X-axis is% value of the output
item.
Example, if the maximum frequency set at dr.20 (Max Freq) is 60 Hz
and the present output frequency is 30 Hz, then the x-axis value on
the next graph is 50%.
Содержание G100
Страница 14: ......
Страница 16: ...5 5 7 5 kW 3 Phase ...
Страница 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Страница 48: ......
Страница 68: ......
Страница 81: ......
Страница 100: ......
Страница 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Страница 118: ......
Страница 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Страница 140: ... PID control block diagram ...
Страница 165: ...Code and Features Description Code Description continuous rating ...
Страница 170: ......
Страница 186: ... Displayed as on the Keypad ...
Страница 200: ...provided signal output at 150 36 sec ...
Страница 216: ...Code and Features Description delay time delay time ...
Страница 219: ......
Страница 237: ......
Страница 253: ......
Страница 295: ......
Страница 314: ......
Страница 330: ...11 10 Remote Keypad Option It is comprised of a remote keypad and cables 1 m 2 m 3 m and 5 m Units mm ...
Страница 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...