5.5 Safe Operation mode
When the multi-function terminals are configured to operate in safe mode, operation
commands can be entered in the Safe operation mode only. Safe operation mode is
used to safely and carefully control the inverter through the multi-function terminals.
Grou
p
Code
Name
Setting
Setting Range
Unit
Ad
70
Safe operation
selection
1
DI Dependent
-
71
Safe operation
stop options
0
Free-Run
0
–2
-
72
Safe operation
deceleration time
5.0
0.0
–600.0
sec
In
65
–69
Px terminal
setting options
13 RUN Enable
0
–52
-
Safe Operation Mode Setting Details
Code and
Features
Description
In.65
–69 Px
Define
From the multi-function terminals, select a terminal to operate in safe
operation mode and set it to 13 (RUN Enable).
Ad.70 Run En
Mode
Configuration
Function
0
Always
Enable
Enables safe operation mode.
1
DI Dependent
Recognizes the operation command from a
multi-function input terminal.
Ad.71 Run Dis
Stop
Set the operation of the inverter when the multi-function input terminal
in safe operation mode is off.
Configuration
Function
1
Free-Run
Blocks the inverter output when the multi-
function terminal is off.
2
Q-Stop
The deceleration time (Q-Stop Time) used in
safe operation mode. Once stopped, the
operation command must be entered again
to restart the operation even if the multi-
function terminal is turned On.
3
Q-Stop
Resume
The inverter decelerates to the deceleration
time (Q-Stop Time) in safe operation mode
and stops. Once stopped, a normal operation
will be continued if the multi-function terminal is
entered again when the operation command is
turned On.
Ad.72 Q-Stop
Sets the deceleration time when Ad.71 (Run Dis Stop) is set to 1 (Q-
Содержание G100
Страница 14: ......
Страница 16: ...5 5 7 5 kW 3 Phase ...
Страница 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Страница 48: ......
Страница 68: ......
Страница 81: ......
Страница 100: ......
Страница 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Страница 118: ......
Страница 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Страница 140: ... PID control block diagram ...
Страница 165: ...Code and Features Description Code Description continuous rating ...
Страница 170: ......
Страница 186: ... Displayed as on the Keypad ...
Страница 200: ...provided signal output at 150 36 sec ...
Страница 216: ...Code and Features Description delay time delay time ...
Страница 219: ......
Страница 237: ......
Страница 253: ......
Страница 295: ......
Страница 314: ......
Страница 330: ...11 10 Remote Keypad Option It is comprised of a remote keypad and cables 1 m 2 m 3 m and 5 m Units mm ...
Страница 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...