4.1.2 Set the Operation Frequency from the Keypad - Using [
▲]
and [
▼] keys
You can use the [
▲] and [▼] keys like a potentiometer to modify the frequency
reference. Select the Frq (Frequency reference source) code in the Operation group
to 1 (Keypad-2). This allows frequency reference values to be increased or decreased
when the [
▲] and [▼] keys are pressed from the Operation group 0.00 (target
frequency).
Group
Code
Name
Setting
Setting Range
Unit
Operation
Frq
Frequency
reference source
1
KeyPad-2
0
–8
-
0.00
Target
frequency
0.00
Min to Max Frq*
Hz
* You cannot set a frequency reference that exceeds the Max. Frequency, as
configured with dr.20.
4.1.3 V1 Terminal as the Source
You can set the frequency by inputting the voltage from the V1 terminal (frequency
setting voltage terminal) from the control terminal block. Use voltage inputs ranging
from 0 to 10 V (unipolar) for forward only operation. Use voltage inputs ranging from -
10 to +10 V (bipolar) for both directions, where negative voltage inputs are used
reverse operations.
4.1.3.1 Setting a Frequency Reference for 0
–10 V Input
Set the Frq (Frequency reference source) code in the Operation group to 2 (V1), and
then set code 06 (V1 Polarity) to 0 (unipolar) in the Input Terminal group (IN). Use the
voltage output of the external controller or use the VR terminal (frequency setting
power terminal) of the control terminal to input voltage in the V1 terminal as the
volume resistance.
[Connecting to external power source]
[Connecting to internal power source]
Содержание G100
Страница 14: ......
Страница 16: ...5 5 7 5 kW 3 Phase ...
Страница 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Страница 48: ......
Страница 68: ......
Страница 81: ......
Страница 100: ......
Страница 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Страница 118: ......
Страница 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Страница 140: ... PID control block diagram ...
Страница 165: ...Code and Features Description Code Description continuous rating ...
Страница 170: ......
Страница 186: ... Displayed as on the Keypad ...
Страница 200: ...provided signal output at 150 36 sec ...
Страница 216: ...Code and Features Description delay time delay time ...
Страница 219: ......
Страница 237: ......
Страница 253: ......
Страница 295: ......
Страница 314: ......
Страница 330: ...11 10 Remote Keypad Option It is comprised of a remote keypad and cables 1 m 2 m 3 m and 5 m Units mm ...
Страница 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...