from the impact of the motor closing and opening (0.4
–4.0 kW models only).
3 Phase 400 V (0.4
–7.5 kW)
Model Name
LSLVG100-4
□□□□□
0004
0008
0015
0022
0040
0055
0075
Applied
motor
Heavy load
HP
0.5
1.0
2.0
3.0
5.0
7.5
10
kW
0.4
0.75
1.5
2.2
4.0
5.5
7.5
Normal
load
HP
1.0
2.0
3.0
5.0
7.5
10
15
kW
0.75
1.5
2.2
4.0
5.5
7.5
11
Rated
output
Rated
capacity
(kVA)
Heavy
load
1.0
1.9
3.0
4.2
6.5
9.1
12.2
Normal
load
1.5
2.4
3.9
5.3
7.6
12.2
17.5
Rated
current (A)
[3-Phase
input]
Heavy
load
1.3
2.5
4.0
5.5
9.0
12.0
16.0
Normal
load
2.0
3.1
5.1
6.9
10.0
16.0
23.0
Rated
current (A)
[1-Phase
input]
Heavy
load
0.7
1.4
2.1
2.8
4.9
6.4
8.7
Normal
load
1.3
1.9
2.8
3.6
5.4
8.7
12.6
Output frequency
0
–400 Hz(IM Sensorless: 0–120 Hz)
Output voltage (V)
3-phase 380
–480 V
Rated
input
Working voltage (V)
3-phase 380
–480 VAC (-15% to +10%)
Single phase 480VAC(-5% to +10%)
Input frequency
50
–60 Hz (
5%)
(In case of single phase input, input frequency is only
60Hz(
5%).)
Rated
current (A)
Heavy
load
1.1
2.4
4.2
5.9
9.8
12.9
17.5
Normal
load
2.0
3.3
5.5
7.5
10.8
17.5
25.4
Weight (lb /kg)
(Built-in EMC filter)
1.02
(1.04)
1.06
(1.08)
1.4
(1.44)
1.42
(1.46)
1.92
(1.98)
3.08
(3.24)
3.12
(3.28)
•
The standard motor capacity is based on a standard 4-pole motor.
•
The standard used for 200 V inverters is based on a 220 V supply voltage, and for
400 V inverters is based on a 440 V supply voltage.
•
The rated output current is limited based on the carrier frequency set at Cn.04.
•
The output voltage becomes 20
–40% lower during no-load operations to protect
the inverter from the impact of the motor closing and opening (0.4
–4.0 kW models
only).
Содержание G100
Страница 14: ......
Страница 16: ...5 5 7 5 kW 3 Phase ...
Страница 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Страница 48: ......
Страница 68: ......
Страница 81: ......
Страница 100: ......
Страница 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Страница 118: ......
Страница 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Страница 140: ... PID control block diagram ...
Страница 165: ...Code and Features Description Code Description continuous rating ...
Страница 170: ......
Страница 186: ... Displayed as on the Keypad ...
Страница 200: ...provided signal output at 150 36 sec ...
Страница 216: ...Code and Features Description delay time delay time ...
Страница 219: ......
Страница 237: ......
Страница 253: ......
Страница 295: ......
Страница 314: ......
Страница 330: ...11 10 Remote Keypad Option It is comprised of a remote keypad and cables 1 m 2 m 3 m and 5 m Units mm ...
Страница 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...