Chapter 12 Compliance with EMC Specifications
12-3
2) Power cable and grounding cable
The grounding/power cable of PLC should be treated as follows.
(1) The panel should be grounded with a thick wire(2 mm
2
or above) to secure a lower impedance even in
high frequency.
(2) LG(Line Ground) terminal and FG(Frame Ground) terminal functionally let the noise inside the PLC flow
into the ground, so a wire of which impedance is low should be used.
(3) Since the grounding cable itself may generate noise, thick and short wiring may prevent it serving as an
antenna.
12.1.3 Cable
1) Extension cable treatment
The extension cable of XGT series is with fast electric signal. Therefore, high frequency noise wave is
emitted from the extension cable. To comply with the CE specifications, please attach the ferrite core on
the extension cable as presented in the figure.
Mode
Manufacturer
Remarks
CU1330D
E Tech Electronics
-
ZCAT3035-1330
TDK
-
2) Fixing a cable in the panel
If the extension cable of XGT series is to be installed on the metallic panel, the cable should be 1cm and
more away from the panel, preventing the direct contact.
The metallic plate of panel may shield noise from electromagnetic wave while it a cable as a noise source
is close to the place, it can serve as an antenna. Every fast signal cable as well as the extension cable
needs proper spacing from the panel.
Ferrite core
Содержание 47200001
Страница 15: ...Table of Content 14 ...
Страница 51: ...Chapter 5 Communication Program 5 16 ...
Страница 55: ...Chapter 6 SyCon Setting 6 4 Select Yes 5 Configuration Setup Select Next ...
Страница 57: ...Chapter 6 SyCon Setting 6 6 3 Setup complete 6 Installed contents 1 Installed file ...
Страница 64: ...Chapter 6 SyCon Setting 6 13 3 Edit 4 Master Configuration Select Settings Master Configuration on menu ...
Страница 73: ...Chapter 6 SyCon Setting 6 22 ...
Страница 99: ...Chapter 7 N Configurator Setting 7 26 ...
Страница 115: ...Chapter 8 High speed Link 8 16 ...
Страница 127: ...Chapter 9 P2P 9 12 ...
Страница 154: ...Chapter 10 Program Example 10 27 Figure 10 2 24 Link Enable High speed link P2P ...
Страница 173: ...Chapter 10 Program Example 10 46 ...
Страница 183: ...Chapter 11 Troubleshooting 11 10 11 4 3 XG5000 abnormal connection ...
Страница 185: ...Chapter 11 Troubleshooting 11 12 ...
Страница 197: ...Appendix A 8 A 3 Dimensions XGL PMEA B C have same dimensions Unit mm ...
Страница 199: ...Warranty and Environment Policy 2 ...