Chapter 11 Troubleshooting
11-11
11.4.4 Abnormal connection with slave module
Is High-speed link
parameter setting correct?
Is power supplied on slave
and master module?
Is the slave station address
setting duplicated?
Is there a problem in serial cable?
Is the cable specified cable
and long length?
Abmornal connection with slave module
Check the High-speed link parameter
Check power slave module
and master module
Check the station address of
slave module and SyCon station address
Check the serial cable connector
Check the cable type and
length in product specifications
Ask to customer service center
Yes
No
No
Yes
Yes
No
No
Yes
No
Yes
Is P2P parameter setting
correct/?
Yes
Check the P2P parameter
No
Содержание 47200001
Страница 15: ...Table of Content 14 ...
Страница 51: ...Chapter 5 Communication Program 5 16 ...
Страница 55: ...Chapter 6 SyCon Setting 6 4 Select Yes 5 Configuration Setup Select Next ...
Страница 57: ...Chapter 6 SyCon Setting 6 6 3 Setup complete 6 Installed contents 1 Installed file ...
Страница 64: ...Chapter 6 SyCon Setting 6 13 3 Edit 4 Master Configuration Select Settings Master Configuration on menu ...
Страница 73: ...Chapter 6 SyCon Setting 6 22 ...
Страница 99: ...Chapter 7 N Configurator Setting 7 26 ...
Страница 115: ...Chapter 8 High speed Link 8 16 ...
Страница 127: ...Chapter 9 P2P 9 12 ...
Страница 154: ...Chapter 10 Program Example 10 27 Figure 10 2 24 Link Enable High speed link P2P ...
Страница 173: ...Chapter 10 Program Example 10 46 ...
Страница 183: ...Chapter 11 Troubleshooting 11 10 11 4 3 XG5000 abnormal connection ...
Страница 185: ...Chapter 11 Troubleshooting 11 12 ...
Страница 197: ...Appendix A 8 A 3 Dimensions XGL PMEA B C have same dimensions Unit mm ...
Страница 199: ...Warranty and Environment Policy 2 ...