Chapter 9 Installation and Wiring
9-
11
9.2.4 Cable Specifications for wiring
The specifications for wiring is as follows:
Cable Specifications (
㎟
)
Kinds of external connection
Minimum
Maximum
Digital Input
0.18 (AWG24)
1.5 (AWG16)
Digital Output
0.18 (AWG24)
2.0 (AWG14)
Analog Input / Output
0.18 (AWG24)
1.5 (AWG16)
Communication
0.18 (AWG24)
1.5 (AWG16)
Main power
1.5 (AWG16)
2.5 (AWG12)
Grounding
1.5 (AWG16)
2.5 (AWG12)
•
Be sure to use solderless terminal for power supply and I/O wiring.
•
Be sure to use M3 type as terminal screw.
•
Make sure that terminal screw is connected by 6
~
9
㎏·㎝
torque..
•
Be sure to use fork shaped terminal screw as shown below.
6.2mm less than
cable solderness terminal (fork shaped)
Содержание MASTER-K80S
Страница 27: ...Chapter 4 Names of Parts 4 4 1 3 30 points base unit 4 1 4 40 points base unit 4 1 5 60 points base unit...
Страница 66: ...Chapter 6 Input and Output Modules 6 3 30 point base unit 4 40 point base unit DC24V DC24V DC24V...
Страница 67: ...Chapter 6 Input and Output Modules 6 5 60 point base unit DC24V DC24V...
Страница 206: ...Chapter 8 Communication Function 8 63 You can see the frame list which is designated Click OK button...