Chapter 8 Communication Function
8-52
(2) SUM 1 , XOR 1 or MUL 1 setting.
a) SUM 1
The last transmitting frame
BCC Type setting
The kinds of
segment input
The value of sum check
ASCII Type
Hex Type
ASCII Input
05 + 31 + 32 +33 +34 +04 = D3
05 31 32 33 34 04 44 33
05 31 32 33 34 04 D3
Hex Input
05 + 12 + 34 +04 = 4F
05 12 34 04 34 46
05 12 34 04 4F
b) XOR 1
The last transmitting frame
BCC Type setting
The kinds of
segment input
The value of sum check
ASCII Type
Hex Type
ASCII Input
05 ^ 31 ^ 32 ^ 33 ^ 34 ^ 04 = 05
05 31 32 33 34 04 30 35
05 31 32 33 34 04 05
Hex Input
05 ^ 12 ^ 34 ^ 04 = 27
05 12 34 04 32 37
05 12 34 04 27
c) MUL 1
The last transmitting frame
BCC Type setting
The kinds of
segment input
The value of sum check
ASCII Type
Hex Type
ASCII Input
05 x 31 x 32 x 33 x 34 x 04 = 60
05 31 32 33 34 04 36 30
05 31 32 33 34 04 60
Hex Input
05 x 12 x 34 x 04 = 20
05 12 34 04 32 30
05 12 34 04 20
d) Complement setting
Complement calculation as below
b
it 7 bit 0
1 1 0 1 0 0 1 1
b
it 7 bit 0
0 0 1 0 1 1 0 0
b
it 7 bit 0
0 0 1 0 1 1 0 1
= h D3(sum check value)
1’ complement = h 2C(the last sum check value)
2’ complement = 1’ comp 1 = h 2D(the last sum check
l )
Содержание MASTER-K80S
Страница 27: ...Chapter 4 Names of Parts 4 4 1 3 30 points base unit 4 1 4 40 points base unit 4 1 5 60 points base unit...
Страница 66: ...Chapter 6 Input and Output Modules 6 3 30 point base unit 4 40 point base unit DC24V DC24V DC24V...
Страница 67: ...Chapter 6 Input and Output Modules 6 5 60 point base unit DC24V DC24V...
Страница 206: ...Chapter 8 Communication Function 8 63 You can see the frame list which is designated Click OK button...