Appendix 2 Flag List
App2-1
Appendix 2. Flag List
1)
Special relay (F)
This flag is useful to edit user program.
Relay
Function
Description
F0000
RUN mode
Turns on when the CPU in the RUN mode.
F0001
Program mode
Turns on when the CPU in the Program mode
F0002
Pause mode
Turns on when the CPU in the Pause mode
F0003
Debug mode
Turns on when the CPU in the Debug mode
F0006
Remote mode
Turns on when the CPU in the Remote mode
F0007
User memory installation
Turns on when a user memory is installed.
F0008 and F0009
Unused
F000A
User memory operation
Turns on when a user memory is being operated
F000B to F000E
Unused
F000F
Execution of the STOP instruction Turns on when the STOP instruction is being operated.
F0010
Always On
Always On
F0011
Always Off
Always Off
F0012
1 Scan On
1 Scan On
F0013
1 Scan Off
1 Scan Off
F0014
Scan toggle
Scan toggle
F0015 to F001F
Unused
F0020
1 step run
Turns on when the 1 step run is operated in the Debug mode.
F0021
Breakpoint run
Turns on when the breakpoint run is operated in the Debug
mode.
F0022
Scan run
Turns on when the scan run is operated in the Debug mode.
F0023
Coincident junction value run
Turns on when the coincident junction run is operated in the
Debug mode.
F0024
Coincident word value run
Turns on when the coincident word run is operated in the Debug
mode.
F0025 to F002F
Unused
F0030
Fatal error
Turns on when a fatal error has occurred.
F0031
Ordinary error
Turns on when an ordinary error has occurred.
F0032
WDT Error
Turns on when a watch dog timer error has occurred.
F0033
I/O combination error
Turns on when an I/O error has occurred.
(When one or more bit(s) of F0040 to F005F turns on)
F0034
Battery voltage error
Turns on when the battery voltage has fallen below the defined
value.
F0035
Fuse error
Turns on when a fuse of output modules has been disconnected.
F0036 to F0038
Unused
F0039
Normal backup operation
Turns on when the data backup is normal.
F003A
RTC data error
Turns on when the RTC data setting error has occurred.
F003B
During program edit
Turns on during program edit while running the program.
F003C
Program edit error
Turns on when a program edit error has occurred while running
the program.
F003D to F003F
Unused
Содержание MASTER-K80S
Страница 27: ...Chapter 4 Names of Parts 4 4 1 3 30 points base unit 4 1 4 40 points base unit 4 1 5 60 points base unit...
Страница 66: ...Chapter 6 Input and Output Modules 6 3 30 point base unit 4 40 point base unit DC24V DC24V DC24V...
Страница 67: ...Chapter 6 Input and Output Modules 6 5 60 point base unit DC24V DC24V...
Страница 206: ...Chapter 8 Communication Function 8 63 You can see the frame list which is designated Click OK button...