Chapter 9 Installation and Wiring
9-
3
(5) Average power consumption of input parts (with points simultaneously ON)
•
W
in
= l
in
×
E
×
input points
×
the rate of points switched on simultaneously (W)
I
in
: input current (effective value for AC) (A)
E : input voltage (actual operating voltage) (V)
(6) Power consumption of the special module
•
W
S
= I
5V
X 5 + I
24V
X 24 (W)
The sum of the above values is the power consumption of the entire PLC system.
•
W = W
PW
+ W
5V
+ W
24V
+ W
out
+ W
in
+ W
s
(W)
Check the temperature rise within the control panel with calculation of that total power
consumption(W). The temperature rise in the control panel is expressed as:
T = W / UA [
°
C]
W : Power consumption of the entire PLC system(obtained as shown above)
A : Control panel inside surface area
[m
2
]
U : if the control panel temperature is controlled by a fan, etc
6
if control panel air is not circulated 4
Содержание MASTER-K80S
Страница 27: ...Chapter 4 Names of Parts 4 4 1 3 30 points base unit 4 1 4 40 points base unit 4 1 5 60 points base unit...
Страница 66: ...Chapter 6 Input and Output Modules 6 3 30 point base unit 4 40 point base unit DC24V DC24V DC24V...
Страница 67: ...Chapter 6 Input and Output Modules 6 5 60 point base unit DC24V DC24V...
Страница 206: ...Chapter 8 Communication Function 8 63 You can see the frame list which is designated Click OK button...