(3) instruction Error List
Error status
Contents
Treatment
00
Normal
-
01
Other PLSOUT instruction pulsating.
Change the other PLCOUT program.
02
Velocity designation error (more than 2000, not a
multiple of 50, designated 0)
Velocity designation adjustment
03
The no. of a/c velocity pulse is bigger than no. of all
pulse is to output.
Acceleration adjustment
04
No output contact point where is designated to the pulse
output
Output contact point designation
05
No output contact point where is designated to the
direction output
Output contact point designation