Chapter 7 Usage of Functions
7- 5 9
7.2.2 A/D Conversion module
1)
Performance specifications
The performance specifications of the analog input module are following
.
Item Specifications
Voltage 0
∼
10VDC ( input resistance more than 1
㏁
)
Current
DC 4
∼
20
㎃
( input resistance 250
Ω
)
DC 0
∼
20
㎃
( input resistance 250
Ω
)
( Classified by parameter )
Analog
input
Voltage/Current
Selection
-.Setting by input terminal
(When current input is used, short the V and I terminal)
- Voltage/Current is selected by KGL-WIN parameter
Digital output
12bit binary (0
∼
4000)
0
∼
10VDC 2.5
㎷
(1/4000)
DC 0
∼
20
㎃
5
㎂
(1/4000)
Maximum
resolution
DC 4
∼
20
㎃
6.25
㎂
(1/3200)
Overall accuracy
±
0.5% [Full Scale]
Max. conversion speed
2
㎳
/CH + scan time
Max. absolute input
Voltage :
±
15V, Current :
±
25
㎃
Number of analog input point
4channels/module
Isolation
Between input terminal and PLC power supply
: Photo coupler isolation
(No isolation between channels)
Terminal connected
2 points/16 points terminal block
Current
Consumption
+5V 100mA
Voltage
DC 21.6 ~ 26.4V
External
Power supply
Current
consumption
100
㎃
Weight 200g
Remark
▶
Offset/Gain value can’t be changed, because it is fixed
▶
Analog inputting is set the current since this is manufactured.
▶
It is possible to use to extend max.2 Modules
▶
The A/D conversion module is possible only to use in more than K80S ROM V1.4,
KGL-WIN V2.14
Содержание MASTER-K80S
Страница 27: ...Chapter 4 Names of Parts 4 4 1 3 30 points base unit 4 1 4 40 points base unit 4 1 5 60 points base unit...
Страница 66: ...Chapter 6 Input and Output Modules 6 3 30 point base unit 4 40 point base unit DC24V DC24V DC24V...
Страница 67: ...Chapter 6 Input and Output Modules 6 5 60 point base unit DC24V DC24V...
Страница 206: ...Chapter 8 Communication Function 8 63 You can see the frame list which is designated Click OK button...