1)
Specifications
Expansion Module
Model
Specification
G7E-DR10A
Number of input points
6 points
Insulation method
Photo coupler
Rated input voltage
DC12 / 24V
Rated input current
4.5 / 9 mA
Operating voltage range
DC10.2 ~ 28.8V (ripple: less than 5%)
Max. Simultaneous input points
100% simultaneously On
On voltage / On current
DC9.5V or higher/ 3.5 mA or higher
Off voltage / Off current
DC5V or lower / 1.8 mA or lower
Input impedance
Approx. 2.7 k
Ω
Off
→
On
15ms or less *
¹
Response time
On
→
Off
15ms or less *
¹
Common terminal
6 points / com
Operating indicator
LED turns on at ON state of input
*
¹
: It’s possible to select from 1ms to 15ms by 1ms at KGLWIN.
2) Circuit diagram
It’s the same with the one for the base unit.
3) Input wiring
DC24V