Chapter 7 Usage of Functions
7- 5 2
3) Parameter setting
The same or less than KGLWIN V2.13
The same or more than KGLWIN V2.14
4) Reading A/D conversion value & Writing D/A conversion value
A/D conversion value and D/A conversion value stores special data register as following.
The table which is shown below is possible to use under the same or less than K80S CPU ROM V1.3.
Special data
register
Explanation Remark
D4980
A/D conversion value of channel 0 stores
D4981
A/D conversion value of channel 1 stores
D4982
D/A conversion value set
A/D
.
D/A combination module #1
D4983
A/D conversion value of channel 0 stores
D4984
A/D conversion value of channel 1 stores
D4985
D/A conversion value set
A/D
.
D/A combination module #2
The table which is shown below is possible to use under the same or more than K80S CPU ROM V1.4.
Special data
register
Explanation Remark
D4980
A/D conversion value of channel 0 stores
D4981
A/D conversion value of channel 1 stores
D4982
D/A conversion value stores
D4983 unused
A/D
.
D/A combination module #1
D4984
A/D conversion value of channel 0 stores
D4985
A/D conversion value of channel 1 stores
D4986
D/A conversion value stores
D4987 unused
A/D
.
D/A combination module #2
Содержание MASTER-K80S
Страница 27: ...Chapter 4 Names of Parts 4 4 1 3 30 points base unit 4 1 4 40 points base unit 4 1 5 60 points base unit...
Страница 66: ...Chapter 6 Input and Output Modules 6 3 30 point base unit 4 40 point base unit DC24V DC24V DC24V...
Страница 67: ...Chapter 6 Input and Output Modules 6 5 60 point base unit DC24V DC24V...
Страница 206: ...Chapter 8 Communication Function 8 63 You can see the frame list which is designated Click OK button...