(1) Introduction
This is a function that carries out the reading of the variable registered by monitor register. This also specifies a registered
number and carries out reading of the variable registered by the number.
(2) PC request Format
Format name
Header
Station No.
Command
Registration No.
Tail
Frame check
Frame (Example)
ENQ H10 Y(y)
H09
EOT BCC
ASCII value
H05
H3130
H59(79) H3039 H03
Item
Explanation
Register No.
Register No. uses the same number registered during monitor register for monitor execution.
It is possible to set from 00-09(H00-H09).
BCC
When command is lowercase(y), only one lower byte of the value resulted by adding 1 byte
each to ASCII values from ENQ to EOT is converted into ASCII, added to BCC.
(3) Response Format(ACK response)
←
In case that the register Format of register No. is the Individual reading of device
Format name
Header
Station
No.
Command
Registratio
n No.
Number of
Blocks
Number of
data
Data
Tail
Frame
check
Frame (Example)
ACK H10 Y(y) H09 H01 H04 H9183AABB
ETX BCC
ASCII value
H06
H3130
H59(79) H3039 H3031
H3034
H3931383341
414242
H03
↑
In case that the register Format of register No. is the continuous reading of device
Format name
Header
Station
No.
Command
Registration
No.
Number of data
Data
Tail
Frame
check
Frame (Example)
ACK H10 Y(y) H09
H04
H9183AABB ETX BCC
ASCII value
H06
H3130
H59(79) H3039 H3034 H3931383341414242
H03
Содержание MASTER-K80S
Страница 27: ...Chapter 4 Names of Parts 4 4 1 3 30 points base unit 4 1 4 40 points base unit 4 1 5 60 points base unit...
Страница 66: ...Chapter 6 Input and Output Modules 6 3 30 point base unit 4 40 point base unit DC24V DC24V DC24V...
Страница 67: ...Chapter 6 Input and Output Modules 6 5 60 point base unit DC24V DC24V...
Страница 206: ...Chapter 8 Communication Function 8 63 You can see the frame list which is designated Click OK button...